background image

14

7.  MAINTENANCE

7.1 Fault finding during commissioning
If  a  BA444DF-F  indicator  fails  to  function  during
commissioning  the  following  procedure  should  be
followed:

Symptom

Cause

Check:

No Display

Instrument not

correctly

connected or

powered.

9 to 22V between

terminals 1 & 2.

When configured

as a listener

displays

‘no ConF’

No inputs are

enabled.

Configuration of

each input.

When configures

as a listener

displays

‘no dAtA’

No data being

received with the

current

configuration.

Device Address

and Variable

Identities are

correct.

That data has

DS-65 format.

Display shows

‘9.9.9.9.9’ with all

decimal points

flashing; all

bargraph

segments

activated and

bargraph scale

flashing.

Value

over-range

Configuration.

and

decimal point

position.

Display shows

‘-9.9.9.9.9’ with

all decimal points

flashing; no

bargraph

segments

activated and

bargraph scale

flashing.

Value

under-range

Configuration

And

decimal point

position.

Display

alternates

between value

and the word

‘bAd’.  Bargraph

flashes.

Status of fieldbus

variable has a

quality of ‘BAD’

or a fault state is

active.

Fieldbus

configuration.

Bargraph scale

flashes.

Process variable

is outside the

limits defined for

the bargraph.

Bargraph

configuration.

All display

segments
activated.

Display is

initialising.

This is normal

operation, after a

few seconds the

model number

followed by the

firmware version
will be displayed

prior to entering

the display

mode.

7.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

Live 

maintenance 

is 

permitted 

on

intrinsically  safe  equipment  installed  in  a
hazardous  area,  but  only  certified  test
equipment  should  be  used  unless  a  gas
clearance certificate is available.

If  a  BA444DF-F  fails  after  it  has  been  functioning
correctly,  the  table  shown  in  section  7.1  may  help
to identify the cause of the failure.

If  this  procedure  does  not  reveal  the  cause  of  the
fault,  it  is  recommended  that  the  instrument  is
replaced.

7.3  Servicing
We  recommend  that  faulty  BA444DF-F  Fieldbus
indicators  are  returned  to  BEKA  associates  or  to
our local agent for repair.

7.4 Routine maintenance
The  mechanical  and  electrical  condition  of  the
instrument  should  be  regularly  checked.    Initially
annual  inspections  are  recommended,  but  the
inspection frequency should be adjusted to suit the
environmental conditions.

7.5  Guarantee
Instruments  which  fail  within  the  guarantee  period
should be returned to BEKA associates or our local
agent.  It is helpful if a brief description of the fault
symptoms is provided.

7.6  Customer comments
BEKA  associates  is  always  pleased  to  receive
comments from customers about our products and
services.    All  communications  are  acknowledged
and 

whenever 

possible, 

suggestions 

are

implemented.

Summary of Contents for FOUNDATION BA444DF-F

Page 1: ...Issue 3 23 rd June 2011 BA444DF F FOUNDATION fieldbus Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...nter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3 11 Scale numeric...

Page 3: ...n alternative version of the fieldbus display order code BA444DF P for use on PROFIBUS PA networks 1 1 Documentation This instruction manual describes ATEX system design and installation of the BA444D...

Page 4: ...ed comply with the Fieldbus Intrinsically Safe Concept FISCO defined in IEC 60079 Part 27 and also have separate entity parameters as shown below FISCO Entity Ui 17 5V dc 22 0V dc Ii 380mA dc 250mA dc...

Page 5: ...any intrinsically safe segment providing The device powering the fieldbus segment is ATEX certified and has output parameters equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provid...

Page 6: ...F F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedur...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA444DF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA444DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA...

Page 16: ...e atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is not...

Page 17: ...sion 1 or 2 Class I Group A B Group C Group D Class II Group E F G Class III Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM and cFM entity parameters are identical to the ATEX parameters a...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...fety parameters and installation requirements The ATEX system design requirements described in section 4 of this manual may therefore be used for IECEx installations in gas atmospheres but the local c...

Page 26: ...ay be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A3 3 Versions of the BA444DF F All versions of the BA444DF F fieldbus indicator have IECEx certification This...

Reviews: