To  enter  the  ‘oFFSt’  function  press  P  which  will
reveal  the  existing  offset  with  one  digit  flashing.
Again  the  flashing  digit  may  be  changed  by
operating the 

 or 

  button and the P  button  will

move  control  to  the  next  digit  or  to  the  decimal
point.  When  ‘oFFSt’  has  been  set  to  the  required
value operating the E button will enter the selection
and  return  to  the  ‘oFFSt’  prompt  in  the  sub-menu.
Three  operations  of  the  E  button  will  return  to  the
‘Edit’ function in the listener configuration menu.

6.3.12 Access code for listener configuration
           menu.        ‘CodE’
Access to the listener menu may be protected by a
four  digit  security  code  which  must  be  entered  to
gain  access.    New  instruments  are  supplied
configured  with  the  default  code  0000  which
disables  this  protection  and  allows  unrestricted
access to the configuration menu.

To  enter  a  new  access  code  select  ‘CodE’  in  the
listener  configuration  menu  by  operating  the 

  or

 button.   To enter the function press P which will

reveal  the  current  access  code  with  one  digit
flashing. The code may be changed using the 

 or

  button  to  adjust  the  flashing  digit  and  the  P

button to move control to the next digit.  When the
required code has been selected, press E to enter
the selection and return to the ‘CodE’ prompt in the
listener configuration menu.    The revised access
code  will  be  activated  when  the  indicator  is
returned to the display mode.

If  the  access  code  is  lost  please  contact  BEKA
associates.

6.3.13 Change from listener to node  ‘tYPE’
This  function  enables  the  instrument  to  be
changed from a fieldbus listener to a fieldbus node
by  selecting  ‘tYPE’  in  the  listener  configuration
menu  using  the 

  or 

  button.    To  enter  the

function  press  P  which  will  show  that  the
instrument  is  configured  as  a  fieldbus  listener,  to
change to a fieldbus node press the 

 or 

 button

which will toggle the display to ‘nodE’   To prevent
accidental    changes  this  request  must  be
confirmed  by  operating  the  P  button  and  entering
‘5urE’.    The  instrument  will  display  ‘0000’  with  the
first digit flashing, using the 

 or 

 button set the

flashing digit to ‘5’ and press the P button to move
control to the next digit  which  should  be  set  to  ‘u’.
When the four letters of ‘5urE’ have been entered,
operating the E button will cause the instrument to
restart as a fieldbus node in the display mode.

CAUTION

All the instrument’s listener configuration
will  be  lost  when  it  is  changed  from  a
fieldbus listener to a fieldbus node.

6.3.14  Reset the indicator to listener factory
            defaults  ‘rESEt’
The  BA444DF-F  indicator  may  be  reset  to  the
listener factory defaults shown below:

Security Code

0000 (disabled)

For each of the eight inputs:

Input enable

Off

Decimal point

Auto (maximum resolution)

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

 To  reset  the  BA444DF-F  indicator  to  the  listener
factory  defaults  select  ‘rESEt’  in  the  listener
configuration  menu  by  operating  the 

  or 

button.      To  enter  the  function  press  P  which  will
reveal  ‘0000’  with  the  left  hand  digit  flashing.    To
prevent accidental use of this function, ‘5urE’ must
be  entered  to  confirm  that  the  instrument  is  to  be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the P button to move control to the next
digit  which  should  be  set  to  ‘u’.    When  the  four
letters of ‘5urE’ have been entered operating the E
button  will  reset  the  BA444DF-F  to  the  factory
defaults.      Any  existing  configuration  and
addresses will be lost when the indicator is reset.

Summary of Contents for FOUNDATION BA444DF-F

Page 1: ...Issue 3 23 rd June 2011 BA444DF F FOUNDATION fieldbus Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...nter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3 11 Scale numeric...

Page 3: ...n alternative version of the fieldbus display order code BA444DF P for use on PROFIBUS PA networks 1 1 Documentation This instruction manual describes ATEX system design and installation of the BA444D...

Page 4: ...ed comply with the Fieldbus Intrinsically Safe Concept FISCO defined in IEC 60079 Part 27 and also have separate entity parameters as shown below FISCO Entity Ui 17 5V dc 22 0V dc Ii 380mA dc 250mA dc...

Page 5: ...any intrinsically safe segment providing The device powering the fieldbus segment is ATEX certified and has output parameters equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provid...

Page 6: ...F F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedur...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA444DF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA444DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA...

Page 16: ...e atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is not...

Page 17: ...sion 1 or 2 Class I Group A B Group C Group D Class II Group E F G Class III Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM and cFM entity parameters are identical to the ATEX parameters a...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...fety parameters and installation requirements The ATEX system design requirements described in section 4 of this manual may therefore be used for IECEx installations in gas atmospheres but the local c...

Page 26: ...ay be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A3 3 Versions of the BA444DF F All versions of the BA444DF F fieldbus indicator have IECEx certification This...

Reviews: