1.  DESCRIPTION

The BA554D is a 4/20mA loop-powered rate
totaliser primarily intended for use with
flowmeters. The instrument simultaneously
displays the rate of flow represent by the
4/20mA input current and the total flow in
engineering units on two separate displays.  The
BA554D only introduces a 1.1V drop which
allows it to be installed into almost any 4/20mA
flow loop.  No additional power supply or battery
is required.

Housed in a robust IP66 glass reinforced
polyester (GRP) enclosure with an armoured
glass window, the BA554D is surface mounting,
or may be pipe mounted using one of the
accessory kits.  A stem mounting kit is also
available allowing direct mounting onto a
flowmeter conduit entry.

2.  OPERATION

Fig 1 shows a simplified block diagram of a
BA554D.  The 4/20mA input current flows
through resistor R1 and forward biased diode
D1.  The voltage developed across D1, which is
relatively constant, is multiplied by a switch
mode power supply and used to power the
instrument.  The voltage developed across R1,
which is proportional to the 4/20mA input
current, provides the input signal for the
analogue to digital converter.

Each time a 4/20mA current is applied to the
instrument, initialisation is performed.  After a
short delay the following display sequence
occurs:

All segments of the display are activated
For about 3 seconds.

Decimal points on large display are
sequentially activated for about 3
seconds.

Rate display and totaliser start to function
using calibration information stored in the
instrument's permanent memory.

If the 4/20mA current is disconnected during
operation the latest total and grand total are
stored in permanent memory.

Fig 1  Simplified block diagram of BA554D

2.1  Controls

The BA554D is controlled and calibrated via four
push-button switches which are located behind
the instrument control cover, or as an option on
the outside of the instrument cover.    In the
display mode i.e. when the instrument is
displaying rate and total flow the switch
functions are:

Summary of Switch Functions

P

Displays input current in mA or as a
percentage of span.

Down

Shows rate display calibration at
4mA input

Up

Shows rate display calibration at
20mA input

E+Down

Grand total –
displays least significant 8 digits

E+Up

Grand total –
displays most significant 8 digits.

Down

 

Resets total display

+Up

programmable function

Note

:  When optional alarms are fitted the push-

buttons may be programmed to have alternative
functions – see section 8.2

Summary of Contents for BA554D

Page 1: ...Issue 1 September 2000 BA554D 4 20mA loop powered field mounting rate totaliser...

Page 2: ...centage clip off 5 15 Local reset of total display 5 16 Security code 5 17 Over and under range 6 Calibration Examples 6 1 Using an external current source 6 2 Using the internal references 7 Maintena...

Page 3: ...ter Each time a 4 20mA current is applied to the instrument initialisation is performed After a short delay the following display sequence occurs All segments of the display are activated For about 3...

Page 4: ...associated annunciators plus a flow indicator as shown on page 1 Rate Shows the flow rate on the smaller Display five digit display Total Shows the total flow since the display instrument was last re...

Page 5: ...two mounting holes are located in a separate compartment with a sealed cover allowing the instrument to be installed without exposing the display assembly Terminals 2 and 4 are internally joined and...

Page 6: ...stallation procedure 4 3 EMC The BA554D complies with the requirements of the European EMC Directive 89 336 EEC For specified immunity all wiring should be in screened twisted pairs with the screens e...

Page 7: ...is displayed on the five digit display Using the instrument s CAL or SEt functions this display may be calibrated to show the flow rate in engineering units Both the zero display at 4mA and the span d...

Page 8: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 9: ...arly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display by With accu...

Page 10: ...ll new BA554D rate totalisers are supplied calibrated as requested at the time of ordering If calibration information is not supplied the BA554D will be set to display a rate of 0 00 with 4mA input an...

Page 11: ...n and 4 20 to display current See section 5 12 Display Description of function SCALE t Total Scale Factor Defines the arithmetic relationship between the rate and total displays May be adjusted betwee...

Page 12: ...ed press E to return to the main menu If the application requires flow rate to be the primary display i e shown on the large display the d P function enables the rate and total displays to be intercha...

Page 13: ...ing the Up and Down buttons and the P button to move to the next digit enter the password SurE Pressing E will then give access to the sub menu Note S is entered as 5 5 9 1 AC rejection FrE WARNING If...

Page 14: ...play rate display divided by Per second tb 1 1 Per minute tb 60 60 Per hour tb 3600 3600 Select the required divisor and press E to return to the main menu 5 12 Function of the P push button C P This...

Page 15: ...flow may be adjusted in one percent increments using the Up or Down buttons When set as required press the E button to enter the revised figure and return to the main programme menu 5 15 Local reset o...

Page 16: ...n using a traceable 4 20mA calibrator Section 6 2 contains an example of calibration using the instruments internal 4 and 20mA references which although not traceable are adequate for many industrial...

Page 17: ...owing decimal point are flashing i e a resolution of 0 1 Press P to move control to the rate display Using the Up or Down push button move the flashing digit to the least significant position right ha...

Page 18: ...ep 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no Toggle this to CLr YES using the U...

Page 19: ...respond by displaying root which is the first function in the main menu Steps Perform as described in previous 3 to 7 calibration example in section 6 1 Step 8 Calibrate the rate display Scroll throug...

Page 20: ...ble to enter the programme mode Incorrect security code entered Enter correct security code or fit security link in override position See Fig 8 7 2 Fault finding after commissioning ENSURE PLANT SAFET...

Page 21: ...still does not function it is likely that the fault is within the protection components on the terminal assembly Terminal assemblies may be exchanged on site providing the replacement includes termina...

Page 22: ...ed as high or low rate or total alarms with normally open or normally closed outputs Fig 9 illustrates the conditions available for a rate alarm and shows which are fail safe i e output is in the alar...

Page 23: ...the alarm function without changing the alarm parameters See section 8 2 3 tYPE Type of alarm Defines whether the alarm operates on the rate or total display See section 8 2 4 SPr1 Alarm setpoint 1 o...

Page 24: ...tYPE This function conditions the alarm to operate on the rate or total display Alarm 1 and Alarm 2 may both be conditioned as rate or total alarms or one may be conditioned for rate and the other fo...

Page 25: ...buttons and the P button to move to the next digit When the required hysteresis has been entered press E to return to the alarm menu e g A BA554D calibrated to display a flow of 0 to 5000 with a high...

Page 26: ...changed by operating the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E twice to return to the AcSP prompt in the Programme Menu Co...

Page 27: ...isplay backlight Reducing the supply voltage below 18V or fitting a curent limiting resistor in series with the supply will reduce the display brilliance 8 4 External push buttons For applications req...

Page 28: ...ault finding during commissioning 7 1 after commissioning 7 2 Flow indicator 2 2 Flow transmitter loops 3 1 Grand total 2 1 clear 5 3 5 10 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 Internal ref...

Page 29: ...struction manual Namely The rate display zero can not be elevated i e 4mA input current must correspond to zero flow 1 and 1 do not flash when the rate display overranges The timebase is identified in...

Reviews: