background image

12

5.4  Root extractor:   root

This function is primarily intended for use with
differential flowmeters which have a square law
4/20mA output.  The root extractor linearises the
flow signal enabling the BA554D to display rate
and total flow in linear engineering units.
To activate the square root extractor select 'root'

from the menu and press

  P

  which will reveal if

the function is 'On' or 'OFF'.   If the function is

set as required, press 

E

 to return to the menu,

or press the 

Up

 or 

Down

 button to change the

setting, followed by the

 E

 button to return to the

main menu.

For reference, the following table shows the
output current from a non-linearised differential
flowmeter.

            

 % of full flow      Current output mA

2.5

4.01

10.0

4.16

25.0

5.00

50.0

8.00

75.0

13.00

100.0

20.00

5.5  Resolution:   rESn

This function defines the resolution of  the least
significant rate display digit.  Decreasing the
display resolution can improve the readability of
a noisy signal.   Select 'rESn' from the menu and

press 

P

 which will reveal the current display

resolution.  To change the resolution press the

Up

 or 

Down

 button to select 1, 2, 5 or 10 digits,

followed by the 

E

 button to return to the menu.

5.6  Position of the decimal points:   d.P.

This function positions the decimal point in both
the rate and total displays.
The rate display can have up to five digits and
the decimal point may be positioned between
any of them, or omitted.   The BA554D uses

floating point arithmetic

 so moving the position

of the rate display decimal point will affect
totalisation.  Similarly the total display has eight
digits and the decimal point may be positioned
between any of them, or may be omitted.

To adjust the position of either decimal points

select 'd.P.' from the main menu and press 

P

which will activate both displays with one digit
and the following decimal point of the total
display flashing. If only the least significant digit
is flashing, this indicates that the decimal point
is omitted.

The position of the decimal point can be moved

by pressing the 

Up

 or 

Down

 push-button.

Operating the 

push-button will toggle control

between the two displays.   When both decimal

points have been correctly positioned press 

E

 to

return to the main menu.

If the application requires flow rate to be the
primary display  i.e. shown on the large display,
the d.P. function enables the rate and total
displays to be interchanged.   The rate display
will continue to have five digits but the total
display will be reduced from eight to six digits.
The rate and total annunciators will also be

interchanged.  Pressing the 

Up

 and 

Down

buttons simultaneously  will interchange the
displays.

5.7  Calibration of rate display using an
       external current source:   CAL

This function enables the zero and span of the
rate display to be adjusted using an external
calibrated current source.  When used with an
accurate traceable current source this is the
preferred method of calibration.

To calibrate the instrument select 'CAL' from the

main menu and press 

P.

  The indicator will

display 'ZErO'  which is a request for a 4mA
input current.  Adjust the external current

calibrator to 4.000mA  and again press 

 which

will reveal the current instrument zero display.
For flow applications this will usually be zero.
Each digit of the rate display can be changed by

pressing the 

Up

 or 

Down

 buttons. When the first

digit is correct pressing 

P

 will transfer control to

the next digit.  The most significant digit, which
can be 1 or 2 is set by rolling over the previous
digit.  When all the digits have been adjusted,

press 

E

 to enter the new zero.  The indicator will

display 'Ent' for a few seconds while the
information is being stored in memory, and will
then return to the 'ZErO' prompt .

To adjust the rate display at 20mA, press the 

Up

button which will cause the instrument to display
'SPAn'. Adjust the external current calibrator to

20.000mA  and again press 

 which will reveal

the existing full scale display.   Each digit of the

rate display can be changed by pressing the 

Up

or 

Down

 buttons. When the first digit is correct

pressing 

P

 will transfer control to the next digit.

The most significant digit, which can be 1 or 2 is
set by rolling over the previous digit.   When all

the digits have been adjusted press 

E t

o enter

the new span.  The instrument will display 'Ent'
for a few seconds while the information is being
stored in memory and will then return to the

'SPAn' prompt.  Finally press 

E

 again to return

to the main menu.

This function may also be used when calibrating
a complete loop from flow to instrument display.

Summary of Contents for BA554D

Page 1: ...Issue 1 September 2000 BA554D 4 20mA loop powered field mounting rate totaliser...

Page 2: ...centage clip off 5 15 Local reset of total display 5 16 Security code 5 17 Over and under range 6 Calibration Examples 6 1 Using an external current source 6 2 Using the internal references 7 Maintena...

Page 3: ...ter Each time a 4 20mA current is applied to the instrument initialisation is performed After a short delay the following display sequence occurs All segments of the display are activated For about 3...

Page 4: ...associated annunciators plus a flow indicator as shown on page 1 Rate Shows the flow rate on the smaller Display five digit display Total Shows the total flow since the display instrument was last re...

Page 5: ...two mounting holes are located in a separate compartment with a sealed cover allowing the instrument to be installed without exposing the display assembly Terminals 2 and 4 are internally joined and...

Page 6: ...stallation procedure 4 3 EMC The BA554D complies with the requirements of the European EMC Directive 89 336 EEC For specified immunity all wiring should be in screened twisted pairs with the screens e...

Page 7: ...is displayed on the five digit display Using the instrument s CAL or SEt functions this display may be calibrated to show the flow rate in engineering units Both the zero display at 4mA and the span d...

Page 8: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 9: ...arly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display by With accu...

Page 10: ...ll new BA554D rate totalisers are supplied calibrated as requested at the time of ordering If calibration information is not supplied the BA554D will be set to display a rate of 0 00 with 4mA input an...

Page 11: ...n and 4 20 to display current See section 5 12 Display Description of function SCALE t Total Scale Factor Defines the arithmetic relationship between the rate and total displays May be adjusted betwee...

Page 12: ...ed press E to return to the main menu If the application requires flow rate to be the primary display i e shown on the large display the d P function enables the rate and total displays to be intercha...

Page 13: ...ing the Up and Down buttons and the P button to move to the next digit enter the password SurE Pressing E will then give access to the sub menu Note S is entered as 5 5 9 1 AC rejection FrE WARNING If...

Page 14: ...play rate display divided by Per second tb 1 1 Per minute tb 60 60 Per hour tb 3600 3600 Select the required divisor and press E to return to the main menu 5 12 Function of the P push button C P This...

Page 15: ...flow may be adjusted in one percent increments using the Up or Down buttons When set as required press the E button to enter the revised figure and return to the main programme menu 5 15 Local reset o...

Page 16: ...n using a traceable 4 20mA calibrator Section 6 2 contains an example of calibration using the instruments internal 4 and 20mA references which although not traceable are adequate for many industrial...

Page 17: ...owing decimal point are flashing i e a resolution of 0 1 Press P to move control to the rate display Using the Up or Down push button move the flashing digit to the least significant position right ha...

Page 18: ...ep 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no Toggle this to CLr YES using the U...

Page 19: ...respond by displaying root which is the first function in the main menu Steps Perform as described in previous 3 to 7 calibration example in section 6 1 Step 8 Calibrate the rate display Scroll throug...

Page 20: ...ble to enter the programme mode Incorrect security code entered Enter correct security code or fit security link in override position See Fig 8 7 2 Fault finding after commissioning ENSURE PLANT SAFET...

Page 21: ...still does not function it is likely that the fault is within the protection components on the terminal assembly Terminal assemblies may be exchanged on site providing the replacement includes termina...

Page 22: ...ed as high or low rate or total alarms with normally open or normally closed outputs Fig 9 illustrates the conditions available for a rate alarm and shows which are fail safe i e output is in the alar...

Page 23: ...the alarm function without changing the alarm parameters See section 8 2 3 tYPE Type of alarm Defines whether the alarm operates on the rate or total display See section 8 2 4 SPr1 Alarm setpoint 1 o...

Page 24: ...tYPE This function conditions the alarm to operate on the rate or total display Alarm 1 and Alarm 2 may both be conditioned as rate or total alarms or one may be conditioned for rate and the other fo...

Page 25: ...buttons and the P button to move to the next digit When the required hysteresis has been entered press E to return to the alarm menu e g A BA554D calibrated to display a flow of 0 to 5000 with a high...

Page 26: ...changed by operating the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E twice to return to the AcSP prompt in the Programme Menu Co...

Page 27: ...isplay backlight Reducing the supply voltage below 18V or fitting a curent limiting resistor in series with the supply will reduce the display brilliance 8 4 External push buttons For applications req...

Page 28: ...ault finding during commissioning 7 1 after commissioning 7 2 Flow indicator 2 2 Flow transmitter loops 3 1 Grand total 2 1 clear 5 3 5 10 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 Internal ref...

Page 29: ...struction manual Namely The rate display zero can not be elevated i e 4mA input current must correspond to zero flow 1 and 1 do not flash when the rate display overranges The timebase is identified in...

Reviews: