background image

2.1  Controls

The indicators are controlled and calibrated via four
front  panel  push  buttons  located  below  the  display.
In  the  display  mode  i.e.  when  the  indicator  is
displaying  a  process  variable,  these  push  buttons
have the following functions:

P

While  this  button  is  pushed  the  indicator
will display the input current in mA, or as a
percentage  of  the  instrument  span
depending  upon  how  the  indicator  has
been  configured.  When  the  button  is
released the normal display in engineering
units will return.  The function of this push
button  is  modified  when  optional  alarms
are fitted to the indicator.

While  this  button  is  pushed  the  indicator
will  display  the  numerical  value  and
analogue bargraph* the indicator has been
calibrated  to  display  with  a  4mA

Φ

 

input.

When  released  the  normal  display  in
engineering units will return.

While  this  button  is  pushed  the  indicator
will  display  the  numerical  value  and
analogue bargraph* the indicator has been
calibrated to display with a 20mA

Φ

 input.

When  released  the  normal  display  in
engineering units will return.

E

No function in the display mode unless the
tare function is being used.

P +

 

Firmware number followed by version.

P + 

Direct access to the alarm setpoints when
optional alarms are fitted to the indicator
and the ‘ACSP’ access setpoints in display
mode function has been enabled.

P + E

Access to configuration menu via optional
security code.

Note:

*

 BA527E-SS 

only

Φ

 

If  the  indicator  has  been  calibrated
using  the  CAL  function,  calibration
points may not be 4 and 20mA.

3.  APPLICATIONS

3.1  Transmitter loops

Both models may be connected in series with any
4/20mA current loop and calibrated to display the
measured variable or control signal in engineering
units.

Figs 2 illustrate a typical application in which an
indicator  is  connected  in  series  with  a  2-wire
transmitter.

Fig 2  Indicator in a transmitter loop

Considering the example shown in Fig 2, the sum
of  the  maximum  voltage  drops  of  all  the
components  in  the  loop  must  be  less  than  the
minimum power supply voltage.

Minimum operating voltage of 2-wire Tx

10.0

Maximum voltage drop caused by controller

5.0

Maximum voltage drop caused by BA507E-SS 1.3
Maximum voltage caused by cables

0.4

                                                                              _____

16.7V

Therefore in this example the power supply must
have a minimum output of 16.7V at 20mA.

3.2  Remote indication

Both  indicators  may  be  driven  from  a  4/20mA
signal to provide a remote indication.   Fig 3 shows
a typical  application in  which  the  4/20mA output
from a gas analyser is connected to a BA507E-SS
loop  powered  indicator  to  provide  a  remote
indication  of  the  analyser’s  output.  Again  it  is
necessary to ensure that the voltage capability of
the 4/20mA source is greater than the sum of the
voltage drops introduced by the indicator and the
cable resistance.

4

Summary of Contents for BA507E-SS

Page 1: ...Issue 2 4th May 2017 BA507E SS BA527E SS Rugged general purpose loop powered panel mounting indicators Issue 2...

Page 2: ...ints to a new indicator 6 3 Under and over range 6 4 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routi...

Page 3: ...be impacted The zero and span of the display are independently adjustable so that the indicator can be calibrated to display any variable represented by the 4 20mA input current e g temperature flow...

Page 4: ...s in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E SS only If the indicator has been calibrated using the CAL function calibration poin...

Page 5: ...b Inspect the indicator s captive gasket and ensure that it is not damaged before inserting the indicator into the panel enclosure aperture c If the enclosure panel is less than 1 0mm thick or is non...

Page 6: ...he panel enclosure in which it is mounted New indicators are supplied with a printed scale card showing the requested units of measurement if this information is not supplied when the indicator is ord...

Page 7: ...the self adhesive printed scale card onto the flexible strip and insert the strip into the indicator as shown below Fig 7 Inserting flexible strip carrying scale card into slot at the rear of indicat...

Page 8: ...Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display mode C...

Page 9: ...9...

Page 10: ...lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to cha...

Page 11: ...A If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an i...

Page 12: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 13: ...ct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct c...

Page 14: ...14...

Page 15: ...wing break point 6 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function...

Page 16: ...e corresponding indicator display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starti...

Page 17: ...tion 7 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20m...

Page 18: ...ut may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both alar...

Page 19: ...19...

Page 20: ...SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low...

Page 21: ...fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press P...

Page 22: ...g access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct set...

Page 23: ...ayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 16 Fig 16 Displayed value and setpoints on bargraph The bargraph ar...

Page 24: ...17 Terminals for optional backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 18 which increases the ma...

Reviews: