background image

To add a break-point using the 

 or 

 button select

'SEt' from the configuration menu and press  

P

 

which

will  result  in  the

 

'Add'  sub-function  prompt  being

displayed.  To enter the sub-function press  

P

 

which

will  reveal  the  current  break-point  and  the  total
number  of  break-points  which  have  already  been
entered.    When adding a break-point the insertion
position  can  be  selected  using  the 

 and  

 push

buttons  followed  by  

P

  push  button  to    insert  the

additional  break-point.    In  previously  uncalibrated
linearisers each new break-point should be added in
front  of  the  highest  existing  break-point,  if  this
sequence is not followed a 'FaiL' message will occur
when the breakpoints are calibrated.  See example in
section 6.2.1.

The delete break-point, sub-function 'dEL' operates in
exactly  the  same  way  as  the  'Add'  sub-function
described above.   Once within the ‘dEL’ function each
time the 

P

 button is pressed a break-point is removed.

When  deleting  a  break-point  from  a  calibrated
indicator,  the  break-point  to  be  deleted  can  be
selected   using   the  

 and  

 push  buttons.    The

minimum  number  of  break-point  is  2,  break-points
'0

:

1' and '1

:

1'.

When the required number of linearising break-point
has been entered, return to the linearisation sub-menu
by pressing 

E

.  

The indicator will display the 'Add' or

'dEL'  prompt  depending  upon  the  last  sub-function
used.  The indicator input current and corresponding
indicator  display  at  each  break-point  can  now  be
entered using the ‘in’ and ‘diSP’ sub-functions.

Using the 

 or 

 button select 'in' from the sub-menu

and press 

P

 which will reveal the starting point for the

first  segment  '0

:

n',   where   n   is   the   total   number   of

break-point entered. Press  

P

 and use the 

 and 

buttons and the  

P

 button to move between digits, to

enter the input current in milliamps at which the first
break-point is required, usually 4.000mA.   When set
as required, press 

E

 to return to the ‘0

:

n’ prompt from

which the next break-point can be selected using the

 and 

 buttons.  When the required break-point has

been selected press  

P

 and enter the indicator input

current at which this break-point is required using the

 and 

 buttons and the 

P

 button to move between

digits,. Repeat this procedure until the indicator input
current at all the break-points has been defined and
then return to the ‘in’ sub-function by pressing the  

E

button.

The  corresponding  indicator  display  at  each  of  the
break-points can now be defined using the ‘diSP’ sub-
function     Using  the  

 and  

 buttons  select  the

‘diSP’ sub-function and press  

P

 which will reveal the

starting point for the first break-point     '0

:

n', where n

is the total number of break-points entered. Press  

P

and use the 

 and 

 buttons and the  

P

 button to

move between digits, to enter the required indicator
display at the first break-point.  When set as required,
press  

E

 to return to the ‘0

:

n’ prompt from which the

next break-point can be selected using the 

 or 

buttons.  When the required break-point has been
selected  press  

P

  and  set  the  required  indicator

display at this break-point.

Repeat this procedure until the indicator display at
all  the  break-points  has  been  defined  and  then
return  to  the  ‘SEt’  function  in  the  configuration
menu by pressing the 

E

 button twice.

Error message

If during calibration the indicator displays a
'FAiL' error message the current at which the
selected break-point is being set is not above
the proceeding break-point or is not below the
following break-point.   

6.2.1  Example 
          Adding break-points to a new indicator

When adding break-points to a new indicator, or to
a  lineariser  following  resetting  to  the  factory
defaults  using  the  'LtAb'  function  described  in
section 6.11, each additional break-point should be
added  before  the  highest  existing  breakpoint.
The  first  additional  break-point  should  be  added
before the default break-point '1

:

1' which will result

in a display of '1

:

2'.   If more new break-points are

required,  using  the  

 button  select  the  new

highest  break-point  '2

:

2'  and  add  the  second

additional  break-point  by  operating  the  

P

 push

button which will result in a display of '2

:

3'.  Repeat

the sequence until the required number of break-
points has been entered.

6.3 Under and over-range

The  lineariser  does  not  change  the  under  and
over-range  indication  described  in  section  6.12.
At input currents below that specified for the first
break-point '0

:

n', the indicator will continue to use

the specified slope of the first segment.

At input currents above that specified for the last
break-point 'n:n', the indicator will continue to use
the slope specified for the last lineariser segment.

6.4  Lineariser default configuration

When the lineariser is reset to the factory defaults
using the ‘LtAb’ function described in section 5.11,
the defaults conditions are:

                                                    

Indicator display

                          BA507E-SS   BA527E-SS

   

First break-point      '0

:

1'    4mA       0.0

       0.00

Second break-point '1

:

1'  20mA 100.0

100.00

16

Summary of Contents for BA507E-SS

Page 1: ...Issue 2 4th May 2017 BA507E SS BA527E SS Rugged general purpose loop powered panel mounting indicators Issue 2...

Page 2: ...ints to a new indicator 6 3 Under and over range 6 4 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routi...

Page 3: ...be impacted The zero and span of the display are independently adjustable so that the indicator can be calibrated to display any variable represented by the 4 20mA input current e g temperature flow...

Page 4: ...s in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E SS only If the indicator has been calibrated using the CAL function calibration poin...

Page 5: ...b Inspect the indicator s captive gasket and ensure that it is not damaged before inserting the indicator into the panel enclosure aperture c If the enclosure panel is less than 1 0mm thick or is non...

Page 6: ...he panel enclosure in which it is mounted New indicators are supplied with a printed scale card showing the requested units of measurement if this information is not supplied when the indicator is ord...

Page 7: ...the self adhesive printed scale card onto the flexible strip and insert the strip into the indicator as shown below Fig 7 Inserting flexible strip carrying scale card into slot at the rear of indicat...

Page 8: ...Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display mode C...

Page 9: ...9...

Page 10: ...lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to cha...

Page 11: ...A If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an i...

Page 12: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 13: ...ct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct c...

Page 14: ...14...

Page 15: ...wing break point 6 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function...

Page 16: ...e corresponding indicator display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starti...

Page 17: ...tion 7 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20m...

Page 18: ...ut may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both alar...

Page 19: ...19...

Page 20: ...SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low...

Page 21: ...fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press P...

Page 22: ...g access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct set...

Page 23: ...ayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 16 Fig 16 Displayed value and setpoints on bargraph The bargraph ar...

Page 24: ...17 Terminals for optional backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 18 which increases the ma...

Reviews: