background image

1.  DESCRIPTION

These rugged panel mounting, general purpose digital
indicators display the current flowing in a 4/20mA loop
in engineering units.  They are loop powered but only
introduce  a  1.2V  drop  which  allows  them  to  be
installed  into  almost  any  4/20mA current  loop.    No
additional power supply or battery is required.

The  two  models  are  electrically  similar,  but  have
different displays.

           Model                          Display

BA507E-SS 

4 digits 15mm high

BA527E-SS

5 digits 11mm high
and 31 segment bargraph.

This  instruction  manual  supplements  the  instruction
sheet supplied with each instrument.

The main application of both models is to display a
measured variable or control signal in a process area.
The indicators have a rugged stainless steel case with
IP66  front  of  panel  ingress  and  impact  protection
allowing them to be installed in environments where
they are liable to be impacted.  The zero and span of
the display are independently adjustable so that the
indicator  can  be  calibrated  to  display  any  variable
represented  by  the  4/20mA  input  current,  e.g.
temperature, flow, pressure or level.

2.  OPERATION

Fig  1  shows  a  simplified  block  diagram  of  both
models.  The 4/20mA input current flows through
resistor  R1  and  forward  biased  diode  D1.    The
voltage  developed  across  D1, which  is  relatively
constant,  is  multiplied  by  a  switch  mode  power
supply  and  used  to  power  the  instrument.    The
voltage developed across R1, which is proportional
to  the  4/20mA input  current,  provides  the  input
signal for the analogue to digital converter.

Each  time  a  4/20mA  current  is  applied  to  the
instrument, initialisation is performed during which
all segments of the display are activated, after five
seconds the instrument displays the input current
using   the   calibration   information   stored   in   the
instrument memory.   If the loop current is too low
to power the instrument the indicator will display
the error message ‘LPLo’.

Fig 1  Indicator block diagram

3

Summary of Contents for BA507E-SS

Page 1: ...Issue 2 4th May 2017 BA507E SS BA527E SS Rugged general purpose loop powered panel mounting indicators Issue 2...

Page 2: ...ints to a new indicator 6 3 Under and over range 6 4 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routi...

Page 3: ...be impacted The zero and span of the display are independently adjustable so that the indicator can be calibrated to display any variable represented by the 4 20mA input current e g temperature flow...

Page 4: ...s in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E SS only If the indicator has been calibrated using the CAL function calibration poin...

Page 5: ...b Inspect the indicator s captive gasket and ensure that it is not damaged before inserting the indicator into the panel enclosure aperture c If the enclosure panel is less than 1 0mm thick or is non...

Page 6: ...he panel enclosure in which it is mounted New indicators are supplied with a printed scale card showing the requested units of measurement if this information is not supplied when the indicator is ord...

Page 7: ...the self adhesive printed scale card onto the flexible strip and insert the strip into the indicator as shown below Fig 7 Inserting flexible strip carrying scale card into slot at the rear of indicat...

Page 8: ...Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display mode C...

Page 9: ...9...

Page 10: ...lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to cha...

Page 11: ...A If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an i...

Page 12: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 13: ...ct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct c...

Page 14: ...14...

Page 15: ...wing break point 6 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function...

Page 16: ...e corresponding indicator display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starti...

Page 17: ...tion 7 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20m...

Page 18: ...ut may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both alar...

Page 19: ...19...

Page 20: ...SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low...

Page 21: ...fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press P...

Page 22: ...g access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct set...

Page 23: ...ayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 16 Fig 16 Displayed value and setpoints on bargraph The bargraph ar...

Page 24: ...17 Terminals for optional backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 18 which increases the ma...

Reviews: