background image

Fig 2  BA374NC powered from floating supply

The sum of the maximum voltage drops of all the
components in the loop must be less than the
minimum power supply voltage.

Minimum operating voltage of BA374NC10.0V

Maximum voltage drop caused by
250ohm load

5.0V

(250ohms x 20mA)

Maximum voltage drop caused by cable  0.2V
resistance  (10ohms x 20mA)

                                                                                
                                                                ---------

Total maximum voltage drop

15.2V

Therefore in this example the power supply must
have an output of greater than 15.2V

5. INSTALLATION

5.1 Location

The BA374NC indicating transmitter can be
supplied in either a glass reinforced polyester
(GRP), or an epoxy painted aluminium enclosure.
Both provide IP66 protection and have a polycar-
bonate window and stainless steel fittings.  The
GRP enclosure is suitable for most industrial instal-
lations including off-shore and waste water treat-
ment applications.  For installations where solvents
may be present, the aluminium enclosure provides
maximum protection.  Both enclosures are surface
mounting, but may be pipe or panel mounted using
the accessory kits described in section 10.

Fig 3  BA374NC installation procedure

To simplify installation, the enclosure may be
installed and the field wiring terminated prior to the
transmitter assembly being fitted.    Terminal 7 is
internally connected to the screen in the GRP
enclosure and to the case in the aluminium
enclosure .

5.2  Installation in Zone 2 hazardous areas

Installations within a Zone 2 hazardous area must
comply with the requirements of BS
EN60079:1997 Part 14.  Both of the instrument
cable entries must be fitted with EEx n or EEx e
approved glands or blanking plugs.

The BA374NC has galvanic input to output
isolation.  This allows an earthed thermocouple or
resistance thermometer to be used providing the
field wiring is able to withstand a 500V rms
insulation test  for one minute

5.3 Installation Procedure

Fig 3 illustrates the instrument installation
procedure.

a. Remove the enclosure cover by unscrewing

the four captive 'A' screws.

b. Remove the transmitter assembly from the

enclosure by unscrewing the three captive 'B'
screws and unplugging the flexible cable(s).

      7

Summary of Contents for BA374NC

Page 1: ...BA374NC Type nL certified field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Page 2: ...brating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD reference 6 8 5 Output current reference 7 Trim Menu 7...

Page 3: ...tion 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you can...

Page 4: ...4...

Page 5: ...mperature measurement applies linearisation using look up tables stored in permanent memory The resulting temperature is shown on the internal display The 4 20mA output current is proportional to the...

Page 6: ...components which may generate a spark in normal operation e g switches and switches and potentiometers These approvals confirm that the BA374NC is safe in normal operation and may be installed in Zone...

Page 7: ...res are surface mounting but may be pipe or panel mounted using the accessory kits described in section 10 Fig 3 BA374NC installation procedure To simplify installation the enclosure may be installed...

Page 8: ...accuracies Each function in the Programme Menu is summa rised in section 6 1 and includes a cross reference to more detailed information in the following sections Although this simple menu driven syst...

Page 9: ...9...

Page 10: ...10...

Page 11: ...can be reached by scrolling through the functions using the Up and Down push buttons as shown in Figs 5A and 5B When returning to the display mode following changes to any parameters the transmitter w...

Page 12: ...See section 6 2 1 For Thermocouple Inputs tYPE Sensor type Selects the type of thermocouple input See section 6 3 1 dEg Units of display Sets display to o C or o F See section 6 3 2 rESn Display reso...

Page 13: ...pressing P will reveal a sub menu from which for thermocouple and resistance thermometer inputs the type of sensor may be selected and associated parameters programmed 6 3 For thermocouple inputs 6 3...

Page 14: ...eit To check or change the display units select dEg from the sub menu and press P to reveal the current setting The setting may be changed by pressing the Up or Down button When the required unit is d...

Page 15: ...20mA output current The transmitter output current is derived from the transmitter display and will change if the display calibration is changed ZEro defines the display at which the output is 4mA an...

Page 16: ...ined in a protected sub menu to minimise the possibility of accidental adjustment Select Cond from the menu and press P The transmitter will display 0000 Using the Up and Down buttons and the P button...

Page 17: ...Pressing P will change the display to 020A and the transmitter output current to approximately 20mA The transmitter output current shown on the external current measuring instrument should be adjusted...

Page 18: ...re of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunciator in the top left hand corner of the displ...

Page 19: ...uple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J us...

Page 20: ...be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the thermocouple temperature Adju...

Page 21: ...osure Before replacing the instrument front cover ensure that the sealing gasket is undamaged and is free from dirt and foreign bodies If a BA374NC fails after it has been functioning correctly the pr...

Page 22: ...eel and the kit contains a trim plate to conceal the edge of the panel aperture 11 0 ALARMS The BA374NC can be supplied with two solid state single pole alarm outputs Each output may be programmed as...

Page 23: ...gain only the functions on alarm 1 are listed but alarm 2 has identical facilities 11 2 Summary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the al...

Page 24: ...24 Fig 11 Programme structure for optional alarms...

Page 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Page 26: ...cSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with this...

Page 27: ...input safety parameters are Ui 30V dc Ii 100mA Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 13 Providing the supply voltage in normal operation...

Reviews: