background image

11.3  Description of programmable functions

The following sections contain detailed descrip-
tions of each programmable function.  They should
be read in conjunction with the programme struc-
ture shown in Fig 11.

11.3.1  Alarm enable:  EnbL

This function allows the alarm to be enabled or
disabled  without altering any of the alarm
parameters.  To check or change the function
select 'EnbL' from the alarm sub-menu and press 

P

which will reveal the current setting.  The function
can be changed by pressing the 

Up

 or 

Down

button followed by the 

E

 button to return to the

'EnbL' prompt.

11.3.2  Setpoint adjustment:   SP1 and SP2

The setpoint of each alarm relates to the
transmitter display and each may be independently
positioned anywhere in the transmitter display
range.  When positioned close to the display limits,
care should be taken to ensure that hysteresis
does not place the alarm beyond the display limits.

To adjust the setpoint select 'SP1' or 'SP2' from
the alarm sub-menu and press 

P

  which will reveal

the existing alarm setpoint.  Each digit of the
setpoint can be adjusted using the 

Up

 and 

Down

push-buttons, and the 

P

 button to move to the next

digit.  When the required setpoint has been
entered press 

 to return the setpoint prompt

'SP1' or 'SP2'.

11.3.3  Alarm function:   HI.LO

Each alarm can be conditioned as a high or low
alarm.   To check or change the alarm function
select 'HI.LO' from the alarm sub-menu and press

P

 to reveal the current setting.  The function can

be changed by pressing the 

Up

 or 

Down

 buttons

followed by the 

E

 button to return the 'HI.LO'

prompt.

11.3.4  Alarm output status:   no.nc

This function allows the alarm output to be open or
to be closed in the alarm condition.  When
deciding which is required, care must be taken to
ensure that the alarm output is fail safe.   
See Fig 8.

WARNING

When the transmitter supply is
removed both alarm outputs will
open irrespective of conditioning.
Therefore for fail safe operation both
alarm outputs should be
programmed to be open in the alarm
condition.

To check or change the alarm output status select
'no.nc' from the alarm sub-menu and press

P

 reveal the current setting.  The function can be

changed by pressing the 

Up

 or 

Down

 button

followed by the 

E

 button to return the 'no.nc''

prompt.

11.3.5  Hysteresis:   HStr

To adjust the hysteresis select 'HStr' from the
alarm sub-menu and press 

P

 which will reveal the

existing figure.  Each digit can be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

P

 button

to move to the next digit.  When the required
hystersis has been entered press 

to return the

'HStr' prompt.
e.g.  A transmitter with a high alarm set at 240 and
hysteresis of 10 will perform as follows:

High alarm will be activated when display
equals or exceeds 240, but will not reset until
the display falls below 230.

11.3.6  Alarm delay:   dELA

This function enables activation of the alarm
output to be delayed for a fixed time following the
alarm condition occurring.  The delay can be
programmed in 1 second increments up to 3600
seconds.  If a delay is not required zero should be
entered.  To adjust the delay select 'dELA' from the
alarm sub-menu and press 

P

 which will reveal the

existing delay.  Each digit of the delay can be
adjusted using the 

Up

 and 

Down

 push-buttons, and

the 

P

  button to move to the next digit.  When the

required delay has been entered press 

to return

the 'dELA' prompt.

11.3.7  Alarm silence time:   SIL

This function is primarily intended for use in small
installations where the alarm output directly
operates an annunciator such as a sounder.  When
the alarm silence time is set to any figure other
than zero, the 

P

 push-button becomes an alarm

accept button.   After an alarm has occurred,
operating the 

P

  button will cause the alarm output

to revert to the non-alarm condition for the
programmed alarm silence time.  The display will
continue to indicate an alarm after it has been
accepted and silenced.   The alarm silence time
may be adjusted between 0 and 3600 seconds in 1
second increments.

To adjust the alarm silence time select 'SIL' from
the alarm sub-menu and press 

P

  which will reveal

the existing time.  Each digit can be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

P

  button

to move to the next digit.  When the required time
has been entered press 

to return the 'SIL'

prompt.

      25

Summary of Contents for BA374NC

Page 1: ...BA374NC Type nL certified field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Page 2: ...brating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD reference 6 8 5 Output current reference 7 Trim Menu 7...

Page 3: ...tion 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you can...

Page 4: ...4...

Page 5: ...mperature measurement applies linearisation using look up tables stored in permanent memory The resulting temperature is shown on the internal display The 4 20mA output current is proportional to the...

Page 6: ...components which may generate a spark in normal operation e g switches and switches and potentiometers These approvals confirm that the BA374NC is safe in normal operation and may be installed in Zone...

Page 7: ...res are surface mounting but may be pipe or panel mounted using the accessory kits described in section 10 Fig 3 BA374NC installation procedure To simplify installation the enclosure may be installed...

Page 8: ...accuracies Each function in the Programme Menu is summa rised in section 6 1 and includes a cross reference to more detailed information in the following sections Although this simple menu driven syst...

Page 9: ...9...

Page 10: ...10...

Page 11: ...can be reached by scrolling through the functions using the Up and Down push buttons as shown in Figs 5A and 5B When returning to the display mode following changes to any parameters the transmitter w...

Page 12: ...See section 6 2 1 For Thermocouple Inputs tYPE Sensor type Selects the type of thermocouple input See section 6 3 1 dEg Units of display Sets display to o C or o F See section 6 3 2 rESn Display reso...

Page 13: ...pressing P will reveal a sub menu from which for thermocouple and resistance thermometer inputs the type of sensor may be selected and associated parameters programmed 6 3 For thermocouple inputs 6 3...

Page 14: ...eit To check or change the display units select dEg from the sub menu and press P to reveal the current setting The setting may be changed by pressing the Up or Down button When the required unit is d...

Page 15: ...20mA output current The transmitter output current is derived from the transmitter display and will change if the display calibration is changed ZEro defines the display at which the output is 4mA an...

Page 16: ...ined in a protected sub menu to minimise the possibility of accidental adjustment Select Cond from the menu and press P The transmitter will display 0000 Using the Up and Down buttons and the P button...

Page 17: ...Pressing P will change the display to 020A and the transmitter output current to approximately 20mA The transmitter output current shown on the external current measuring instrument should be adjusted...

Page 18: ...re of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunciator in the top left hand corner of the displ...

Page 19: ...uple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J us...

Page 20: ...be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the thermocouple temperature Adju...

Page 21: ...osure Before replacing the instrument front cover ensure that the sealing gasket is undamaged and is free from dirt and foreign bodies If a BA374NC fails after it has been functioning correctly the pr...

Page 22: ...eel and the kit contains a trim plate to conceal the edge of the panel aperture 11 0 ALARMS The BA374NC can be supplied with two solid state single pole alarm outputs Each output may be programmed as...

Page 23: ...gain only the functions on alarm 1 are listed but alarm 2 has identical facilities 11 2 Summary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the al...

Page 24: ...24 Fig 11 Programme structure for optional alarms...

Page 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Page 26: ...cSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with this...

Page 27: ...input safety parameters are Ui 30V dc Ii 100mA Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 13 Providing the supply voltage in normal operation...

Reviews: