11.3.8  Access Setpoint:  AcSP

This function controls the parameters in a separate
menu which provides direct access to the alarm
setpoints when the transmitter is in the display
mode i.e. when it is displaying temperature.  See
section 11.4 for a full description.    This menu
allows an operator to adjust the two alarm
setpoints without having access to the Programme,
Trim or Alarm Menus.  A separate security code
may be defined to prevent unauthorised access.

This separate direct access menu is enabled and a
separate security code entered from the 'AcSP'
function in the Programme Menu - see Fig 11.  To
change the menu parameters select 'AcSP' from
the Programme Menu and press 

P

  which will

display the enable prompt 'EnbL'.  Press 

P

 again to

reveal if the direct access menu is 'On' or 'OFF'.
The 

Up

 or 

Down

 buttons will toggle the display

between the two conditions.  

If 'OFF' is selected, the operator will not have
access to the setpoints from the display mode.
Return to the 'AcSP' prompt in the main menu by
pressing

 E

 twice.  

If 'On' is selected, the operator will have direct
access to the alarm setpoints from the display
mode via a separate optional security code.   To
define the four digit numerical code press 

P

 to

return to the 'Enbl' prompt followed by the 

Up

 or

Down

 button to select the access code prompt

'AcCd'.   Pressing 

will reveal the current security

code.  Each digit of the code may be changed by
operating the 

Up

 and 

Down

 push-buttons, and the

P

 button to move to the next digit.  When the

required code has been entered, press 

E

 twice to

return to the 'AcSP' prompt in the Programme
Menu.

Code 0000 will disable the security code allowing
direct access to the setpoints by pressing the

  P

and 

Up

 buttons simultaneously.

New instruments are supplied with this function
disabled and the security code set to 0000

11.4  Adjusting the alarm setpoints from the

   display mode.

Access to the alarm setpoint when the BA374NC
transmitter is in the display mode is obtained by
operating the 

P

 and 

Up

 push-buttons simultane-

ously - see Fig 12.   If the setpoints are not
protected by a security code the alarm setpoint one
'SP1' will be displayed.  If the setpoints are
protected by a security code,  'COdE' will be
displayed first.  Pressing 

P

 again will  enable the

alarm security code to be entered digit by digit
using the 

Up

 and 

Down

 buttons to change the

flashing digit, and the 

P

  push-button to move to

the next digit.   If the correct code is entered press-
ing 

E

 will cause alarm setpoint one 'SP1' to be

displayed.  Pressing the 

Up

 or 

Down

 button will

toggle the display between 'SP1' and 'SP2'.  

Fig 12  Setpoint adjustment from display mode

If an incorrect code is entered, or a button is not
pressed for ten seconds, the transmitter will
automatically return to the display mode. 

To adjust an alarm setpoint select 'SP1' or 'SP2'
and press 

P

  which will reveal the current setting.

Each digit of the setpoint may be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

button

to move to the next digit.  When the required
setpoint has been entered, pressing  

E

  will return

the display to the 'SP1' or 'SP2' prompt from which
the other setpoint may be selected, or the transmit-
ter may be returned to the display mode by press-
ing 

E

 again.

Direct access to the alarm setpoints is only avail-
able when the menu is enabled - see section
11.3.8

      26

Summary of Contents for BA374NC

Page 1: ...BA374NC Type nL certified field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Page 2: ...brating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD reference 6 8 5 Output current reference 7 Trim Menu 7...

Page 3: ...tion 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you can...

Page 4: ...4...

Page 5: ...mperature measurement applies linearisation using look up tables stored in permanent memory The resulting temperature is shown on the internal display The 4 20mA output current is proportional to the...

Page 6: ...components which may generate a spark in normal operation e g switches and switches and potentiometers These approvals confirm that the BA374NC is safe in normal operation and may be installed in Zone...

Page 7: ...res are surface mounting but may be pipe or panel mounted using the accessory kits described in section 10 Fig 3 BA374NC installation procedure To simplify installation the enclosure may be installed...

Page 8: ...accuracies Each function in the Programme Menu is summa rised in section 6 1 and includes a cross reference to more detailed information in the following sections Although this simple menu driven syst...

Page 9: ...9...

Page 10: ...10...

Page 11: ...can be reached by scrolling through the functions using the Up and Down push buttons as shown in Figs 5A and 5B When returning to the display mode following changes to any parameters the transmitter w...

Page 12: ...See section 6 2 1 For Thermocouple Inputs tYPE Sensor type Selects the type of thermocouple input See section 6 3 1 dEg Units of display Sets display to o C or o F See section 6 3 2 rESn Display reso...

Page 13: ...pressing P will reveal a sub menu from which for thermocouple and resistance thermometer inputs the type of sensor may be selected and associated parameters programmed 6 3 For thermocouple inputs 6 3...

Page 14: ...eit To check or change the display units select dEg from the sub menu and press P to reveal the current setting The setting may be changed by pressing the Up or Down button When the required unit is d...

Page 15: ...20mA output current The transmitter output current is derived from the transmitter display and will change if the display calibration is changed ZEro defines the display at which the output is 4mA an...

Page 16: ...ined in a protected sub menu to minimise the possibility of accidental adjustment Select Cond from the menu and press P The transmitter will display 0000 Using the Up and Down buttons and the P button...

Page 17: ...Pressing P will change the display to 020A and the transmitter output current to approximately 20mA The transmitter output current shown on the external current measuring instrument should be adjusted...

Page 18: ...re of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunciator in the top left hand corner of the displ...

Page 19: ...uple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J us...

Page 20: ...be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the thermocouple temperature Adju...

Page 21: ...osure Before replacing the instrument front cover ensure that the sealing gasket is undamaged and is free from dirt and foreign bodies If a BA374NC fails after it has been functioning correctly the pr...

Page 22: ...eel and the kit contains a trim plate to conceal the edge of the panel aperture 11 0 ALARMS The BA374NC can be supplied with two solid state single pole alarm outputs Each output may be programmed as...

Page 23: ...gain only the functions on alarm 1 are listed but alarm 2 has identical facilities 11 2 Summary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the al...

Page 24: ...24 Fig 11 Programme structure for optional alarms...

Page 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Page 26: ...cSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with this...

Page 27: ...input safety parameters are Ui 30V dc Ii 100mA Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 13 Providing the supply voltage in normal operation...

Reviews: