BEKA BA374NC Manual Download Page 6

3. TYPE 'n' CERTIFICATION

3.1 Certificate of Assurance

BASEEFA has issued the BA374NC with a
Certificate of Assurance BAS No. 96Y4522
confirming compliance with BS6941:1988.  This
verifies that in normal operation the BA374NC is
not capable of igniting a surrounding explosive
atmosphere, and a fault capable of causing ignition
is not likely to occur. 

3.2 ATEX certification

The BA374NC complies with the European ATEX
Directive 94/9/EC for Group II, Category 3G
equipment.  It has been assessed using the
'Internal Control of Production' procedure specified
in Annex 8 of the Directive.  A Technical Dossier
has been prepared and a EC Declaration of
Conformity number N0014 has been issued.

The instrument bears the Community Mark and,
subject to local codes of practice, may be installed
in any of the European Economic Area (EEA)
member countries.  i.e. Austria, Belgium,
Denmark, Finland, France, Germany, Greece,
Ireland, Italy, Luxembourg, The Netherlands,
Portugal, Spain, Sweden, and the United Kingdom.
 ATEX certificates are also accepted in Norway,
Iceland, Liechtenstein, Switzerland and the Czech
Republic.  This manual describes installations
which conform with BS EN60079:Part14:1997
Electrical Installation in Hazardous Areas.  When
designing systems for installation outside the UK,
the local code of practice should be consulted.

3.3  Zones, gas groups and T rating

The BA324NC has an EEx nL IIC T5, Tamb -40 to
60

o

C safety code as defined in BS EN50021:1999

Electrical apparatus for potentially explosive
atmospheres - Type of protection 'n'.

'L' indicates that the BA374NC uses an
energy-limiting technique to achieve compliance
as defined in Clause 21 of BS EN50021:1999.
This technique is based on the philosophy of
intrinsic safety which limits the current and voltage
applied to components which may generate a
spark in normal operation e.g. switches and
switches and potentiometers.

These approvals confirm that the BA374NC is
'safe in normal operation' and may be installed in:

Zone 2 explosive gas air mixture not

likely to occur, and if it does, it
will only exist for a short time.

Be used with gases in groups:

Group   A

propane

Group   B

ethylene

Group   C

hydrogen

Having a temperature classification of:

T1

450

o

C

T2

300

o

C

T3

200

o

C

T4

135

o

C

T5

100

o

C

This allows the BA374NC to be installed in Zone 2
and to be used with most common industrial
gases.

3.4  Certification label information

Certification information is shown on a label fitted
in a recess on the top outer surface of the
enclosure.  It shows the ATEX certification
information and the Certificate of Assurance with
BS6941:1988.  The instrument serial number and
date of manufacture are shown on a separate label
within the enclosure.

4. ELECTRICAL SYSTEM DESIGN FOR 
    INSTALLATION IN  HAZARDOUS  AREAS

There are two basic requirements when designing
a loop incorporating a BA374NC:

1.

To comply with the EEx nL certification, in
normal operation  i.e. without any faults, the
safe area power supply must have an output
voltage of  less than 30V.   
The safety compents within the BA374NC
will automatically ensure that the output
current does not exceed 25mA in normal
operation.

2.

To ensure correct operation of the
transmitter the voltage between terminals 5
& 6 of the BA374NC must be between 10
and 30V at all output currents.

Fig 2 illustrates a typical temperature measuring
loop.  The  BA374NC is located in Zone 2 and
powered from a supply in the safe area.

WARNING

The enclosure cover should only be
removed when the measurement loop
is not energised, or when there is no
risk of a flammable atmosphere being
present and dust or water can not enter
the enclosure.  Before replacing the
enclosure cover ensure that the sealing
gasket is undamaged and is free from
dirt and foreign bodies.

      6

Summary of Contents for BA374NC

Page 1: ...BA374NC Type nL certified field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Page 2: ...brating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD reference 6 8 5 Output current reference 7 Trim Menu 7...

Page 3: ...tion 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you can...

Page 4: ...4...

Page 5: ...mperature measurement applies linearisation using look up tables stored in permanent memory The resulting temperature is shown on the internal display The 4 20mA output current is proportional to the...

Page 6: ...components which may generate a spark in normal operation e g switches and switches and potentiometers These approvals confirm that the BA374NC is safe in normal operation and may be installed in Zone...

Page 7: ...res are surface mounting but may be pipe or panel mounted using the accessory kits described in section 10 Fig 3 BA374NC installation procedure To simplify installation the enclosure may be installed...

Page 8: ...accuracies Each function in the Programme Menu is summa rised in section 6 1 and includes a cross reference to more detailed information in the following sections Although this simple menu driven syst...

Page 9: ...9...

Page 10: ...10...

Page 11: ...can be reached by scrolling through the functions using the Up and Down push buttons as shown in Figs 5A and 5B When returning to the display mode following changes to any parameters the transmitter w...

Page 12: ...See section 6 2 1 For Thermocouple Inputs tYPE Sensor type Selects the type of thermocouple input See section 6 3 1 dEg Units of display Sets display to o C or o F See section 6 3 2 rESn Display reso...

Page 13: ...pressing P will reveal a sub menu from which for thermocouple and resistance thermometer inputs the type of sensor may be selected and associated parameters programmed 6 3 For thermocouple inputs 6 3...

Page 14: ...eit To check or change the display units select dEg from the sub menu and press P to reveal the current setting The setting may be changed by pressing the Up or Down button When the required unit is d...

Page 15: ...20mA output current The transmitter output current is derived from the transmitter display and will change if the display calibration is changed ZEro defines the display at which the output is 4mA an...

Page 16: ...ined in a protected sub menu to minimise the possibility of accidental adjustment Select Cond from the menu and press P The transmitter will display 0000 Using the Up and Down buttons and the P button...

Page 17: ...Pressing P will change the display to 020A and the transmitter output current to approximately 20mA The transmitter output current shown on the external current measuring instrument should be adjusted...

Page 18: ...re of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunciator in the top left hand corner of the displ...

Page 19: ...uple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J us...

Page 20: ...be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the thermocouple temperature Adju...

Page 21: ...osure Before replacing the instrument front cover ensure that the sealing gasket is undamaged and is free from dirt and foreign bodies If a BA374NC fails after it has been functioning correctly the pr...

Page 22: ...eel and the kit contains a trim plate to conceal the edge of the panel aperture 11 0 ALARMS The BA374NC can be supplied with two solid state single pole alarm outputs Each output may be programmed as...

Page 23: ...gain only the functions on alarm 1 are listed but alarm 2 has identical facilities 11 2 Summary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the al...

Page 24: ...24 Fig 11 Programme structure for optional alarms...

Page 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Page 26: ...cSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with this...

Page 27: ...input safety parameters are Ui 30V dc Ii 100mA Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 13 Providing the supply voltage in normal operation...

Reviews: