background image

    * Worst case high resolution figures are

quoted, at most temperatures resolution will
be greater.

6.3.4 Cold junction compensation  'CJC'

The temperature of the transmitter input terminals,
which is the thermocouple cold junction,  is
measured and added to the output from the
thermocouple so that the transmitter displays and
transmits the temperature relative to zero degrees
centigrade or Fahrenheit.  If cold junction
compensation is not required, e.g. for differential
measurement with two thermocouples, this
function enables the cold junction compensation to
be turned off.

To turn the cold junction compensation on or off
select 'CJC' from the sub-menu and press 

P

 to

reveal the current status.  The setting may be
changed by pressing the 

Up

 or 

Down

 button. When

set as required press 

E

 to return to the sub-menu.

6.3.5  Input open circuit drive  'burn'

If the thermocouple fails and becomes open circuit,
the transmitter can be conditioned to drive the
display and the 4/20mA output current up or down
into a safe condition.  Alternatively the drive may
be turned off which will result in the display and the
4/20mA output current drifting towards zero. 
To check or change the input open circuit drive
select 'burn' from the sub-menu and press 

P

 to

reveal the current setting.  The setting may be
changed by pressing the 

Up

 or 

Down

 button. When

the required setting has been selected, press 

E

 to

return to the sub-menu.

6.4  For resistance thermometer inputs

6.4.1 Types of resistance thermometer 'tYPE'

The transmitter may be conditioned to accept
3-wire, 4-wire or differential Pt100 resistance
thermometers.  
After selecting resistance thermometer input from
the 'InPut' sub-menu,  press 

P

 to reveal the 'tYPE'

sub-menu. Press 

P

 again to display the current

type resistance thermometer which may be
changed by scrolling through the menu using the

Up

 or 

Down

 buttons.  When the required type is

displayed, press 

E

 to return to the sub-menu.

6.4.2  Display units  'dEg'

The transmitter display may be in degrees
centigrade or Fahrenheit.  To check or change the
display units select 'dEg' from the sub-menu and
press 

P

 to reveal the current setting.  The setting

may be changed by pressing the 

Up

 or 

Down

button. When the required unit is displayed, press

E

 to return to the sub-menu.

6.4.3 Display resolution  'rESn'

The output of the resistance thermometer can be
displayed with high or low resolution as shown
below.   Low resolution can improve the readability
of a noisy or rapidly changing display, but does not
degrade the performance of the 4/20mA analogue
output.  High resolution is only available when the
transmitter is displaying temperature in 

o

C. When

o

F is selected the resolution is always one degree.

To check or change the display resolution select
'rESn' from the sub-menu and press 

to reveal

the current setting.  The setting may be changed
by pressing the 

Up

 or 

Down

 button. When the

required resolution has been selected, press 

E

 to

return to the sub-menu.

                         

 Display Resolution

                         Low                    High

1

o

C

0.1

o

C

6.5  For Voltage Inputs

When the transmitter is conditioned for a voltage
input both the input voltage range and the
corresponding display must be programmed.

6.5.1  Position of display decimal point   'd.P.

'

A dummy decimal point can be positioned between
any of the display digits or it may be absent.  
After selecting voltage input from the 'InPut' menu,
 press 

P

  to reveal the 'd.P.' sub-menu. Press 

P

again to display the current decimal point position.
The decimal point can be moved or turned off by
pressing the 

Up

 or 

Down

 push-button, followed by

E

 to return to the sub-menu.

6.5.2  Low input & display calibration  'In-LO'

This function defines the lower voltage input and
the corresponding transmitter display.   See
example below:
 
         

   Input      Transmitter

             mV           Display

-10.00

-3.000

Low input / display

12.55 

3.765

High input / display

The calibration is performed using the internal
references and may be made with any transmitter
input voltage.

Select 'In-LO' from the menu and press 

P

 which

will access a sub-menu containing two functions
'InPut' and ''dISP'.   

Select the input voltage 'InPut' and press 

P

 which

will cause the specified lower input millivoltage to
be displayed in the form XX.XX The flashing digit
of  the  input  voltage  can  be changed by pressing

      14

Summary of Contents for BA374NC

Page 1: ...BA374NC Type nL certified field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Page 2: ...brating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD reference 6 8 5 Output current reference 7 Trim Menu 7...

Page 3: ...tion 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you can...

Page 4: ...4...

Page 5: ...mperature measurement applies linearisation using look up tables stored in permanent memory The resulting temperature is shown on the internal display The 4 20mA output current is proportional to the...

Page 6: ...components which may generate a spark in normal operation e g switches and switches and potentiometers These approvals confirm that the BA374NC is safe in normal operation and may be installed in Zone...

Page 7: ...res are surface mounting but may be pipe or panel mounted using the accessory kits described in section 10 Fig 3 BA374NC installation procedure To simplify installation the enclosure may be installed...

Page 8: ...accuracies Each function in the Programme Menu is summa rised in section 6 1 and includes a cross reference to more detailed information in the following sections Although this simple menu driven syst...

Page 9: ...9...

Page 10: ...10...

Page 11: ...can be reached by scrolling through the functions using the Up and Down push buttons as shown in Figs 5A and 5B When returning to the display mode following changes to any parameters the transmitter w...

Page 12: ...See section 6 2 1 For Thermocouple Inputs tYPE Sensor type Selects the type of thermocouple input See section 6 3 1 dEg Units of display Sets display to o C or o F See section 6 3 2 rESn Display reso...

Page 13: ...pressing P will reveal a sub menu from which for thermocouple and resistance thermometer inputs the type of sensor may be selected and associated parameters programmed 6 3 For thermocouple inputs 6 3...

Page 14: ...eit To check or change the display units select dEg from the sub menu and press P to reveal the current setting The setting may be changed by pressing the Up or Down button When the required unit is d...

Page 15: ...20mA output current The transmitter output current is derived from the transmitter display and will change if the display calibration is changed ZEro defines the display at which the output is 4mA an...

Page 16: ...ined in a protected sub menu to minimise the possibility of accidental adjustment Select Cond from the menu and press P The transmitter will display 0000 Using the Up and Down buttons and the P button...

Page 17: ...Pressing P will change the display to 020A and the transmitter output current to approximately 20mA The transmitter output current shown on the external current measuring instrument should be adjusted...

Page 18: ...re of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunciator in the top left hand corner of the displ...

Page 19: ...uple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J us...

Page 20: ...be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the thermocouple temperature Adju...

Page 21: ...osure Before replacing the instrument front cover ensure that the sealing gasket is undamaged and is free from dirt and foreign bodies If a BA374NC fails after it has been functioning correctly the pr...

Page 22: ...eel and the kit contains a trim plate to conceal the edge of the panel aperture 11 0 ALARMS The BA374NC can be supplied with two solid state single pole alarm outputs Each output may be programmed as...

Page 23: ...gain only the functions on alarm 1 are listed but alarm 2 has identical facilities 11 2 Summary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the al...

Page 24: ...24 Fig 11 Programme structure for optional alarms...

Page 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Page 26: ...cSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with this...

Page 27: ...input safety parameters are Ui 30V dc Ii 100mA Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 13 Providing the supply voltage in normal operation...

Reviews: