40
P1
OPTIONAL
OPTIONAL
4/20mA
OUTPUT
C1
C2
PULSE
OUPUT
P2
B2
BACKLIGHT
OPTIONAL
B1
EQUIPMENT
UNCLASSIFIED
LOCATION
REMOTE
RESET
7
8
POWER
SUPPLY
1
2
BA338C
BA334D
OPTIONAL
ALARM
A1
A2
ALARM
OPTIONAL
A4
A3
SEE NOTE 1 & 2
BA338C LOCATIONS:
Class I, Division 2, Groups A, B,C, D
Class I, Zone 2, Group IIC
BA334D LOCATIONS:
Class I, Division 2, Groups A, B,C, D
Class II, Division 2, Groups E, F & G
Class III
Class I, Zone 2, Group IIC
or
SEE NOTES 5 & 7
SEE NOTE 4
INPUT IN HAZARDOUS (CLASSIFIED) LOCATION
HAZARDOUS (CLASSIFIED) LOCATION
UNCLASSIFIED LOCATION
SEE
NOTE 7
VOLTAGE PULSE,
PROXIMITY DETECTOR
OR SWITCH CONTACT
SEE NOTE 3
VOLTAGE PULSE
SEE NOTE 3
5
6
INPUT
3
4
INPUT
BA334D & BA338C
Terminals 1 & 2
Vmax = 30V
Ci = 0.02µF
Li = 0.02mH
Terminals 7 & 8
Vmax = 30V dc Voc = 3.8V dc
Ci = 0.02µF Isc = 1.6mA
Li = 0mH Ca = 1000µF
La = 1000mH
Terminals B1 & B2
Vmax = 30V dc
Ci = 0.04µF
Li = 0.03mH
Terminals P1 & P2
Vmax = 30V dc
Ci = 0.02µF
Li = 0.02mH
Terminals C1 & C2
Vmax = 30V dc
Ci = 0.002µF
Li = 0.008mH
Terminals 3 & 4
Vmax = 30V dc Voc = 1.1V dc
Ci = 0.02µF Isc = 0.5mA dc
Li = 0.02mH Ca = 1000µF
La = 1000mH
Terminals 5 & 6
Vmax = 30V dc Voc = 10.5V dc
Ci = 0.02µF Isc = 9.2mA dc
Li = 0.02mH Ca = 2.39µF
La = 300mH
Terminals A1 & A2 and A3 & A4
Vmax = 28V dc
Ci = 0.04µF
Li = 0.03mH
Summary of Contents for BA334D
Page 12: ...12 Fig 7 Dimensions and terminal connections ...
Page 14: ...14 ...