22
Step 11 Reset the grand total to zero
Before completing commissioning
the grand total counter should be
reset to zero. Select 'CLr. Gtot'
from the main menu and press P
which will cause the instrument to
display 'Clr. no'. Toggle this to
'CLr. YES' using the Up or Down
push-buttons and press P which will
result in a '0000' prompt. Using the
Up, and Down buttons and the P
button to move to the next digit,
confirm the request by entering the
password 'SurE'. Note: S is entered
as 5. Pressing E will then reset
the grand total counter to zero and
return the instrument to the 'CLr.
Gtot' prompt in the main menu.
Step 12 Define the security code
Defining a security code prevents
unauthorised access to the
programme functions. Select
'COdE' from the main menu and
press P which will reveal the
existing security code. Using the
Up and Down buttons enter the
new code 1209 digit by digit. The P
button will transfer control between
digits. When the new code has
been entered, press E to return to
the main programme menu.
Step 13 Return to the display mode
Following completion of
programming and calibration, return
the BA334D to the operating mode
by pressing E. All the
programming functions will now be
stored in permanent memory and
will be protected by the security
code from accidental or
unauthorised adjustment.
Summary of Contents for BA334D
Page 12: ...12 Fig 7 Dimensions and terminal connections ...
Page 14: ...14 ...