2.2 Controls
The BA317NE is controlled and configured via four
front panel push buttons. In the display mode i.e.
when the instrument is displaying speed the push
button functions are:
Push Button Functions
&
+
*
To reset run-time to zero press buttons
simultaneously for three seconds or
longer. This is a configurable function.
See 6.15
)
+
*
To reset grand total run-time to zero
press buttons simultaneously for ten
seconds or longer. This is a configurable
function.
See 6.16
(
+
&
Shows in succession, firmware version
number, instrument function
tacho
and
any output accessories that are fitted:
- A
Dual alarm outputs
- P
Pulse output
- C
4/20mA output
(
+
)
Access to configuration menu
Note
: When optional alarms are fitted, the
Tachometer may be configured to provide direct
access to the alarm setpoints from the display mode
when the
(
+
*
buttons are operated.
See 9.4.13 and 9.4.14
2.3 Displays
The BA317NE has two digital displays and
associated annunciators, plus a pulse input indicator
as shown on front cover of this manual.
Speed
On upper eight digit display
display
Run-time
On lower six digit display.
display
Shows time in hours, with a
resolution of 0.1 hours, that
monitored machinery has been
operating. May be turned off.
See 6.8
Pulse input
This disc in the lower left hand
indicator
corner of the display 'rotates'
for two seconds each time an
input pulse is received.
Appears to rotate continuously
when input frequency exceeds
0.5Hz.
Hold
Activated when input frequency
annunciator
is below the clip-off threshold at
which the run-time timer stops
functioning.
Reset
Activated while run-time display
annunciator
is being reset to zero.
Grand total
Activated while run-time grand
annunciator
total which is shown in hours is
being displayed.
RTx
Retransmitted pulse
annunciator
annunciator.
Depends upon the setting of
5ource
in the pulse output
configuration menu.
5caled:
Annunciator activated each
time pulse output open
collector is
on
, i.e. Ron is
less than 60
Ω
+ 3V.
direct:
Annunciator
c
ontinuously
activated.
6