background image

9.4.9  Hysteresis:  

H5tr

Hysteresis is only available on speed alarms so the

H5tr

 function only appears in the configuration sub-

menu when alarm 

tYPE

 has been set to 

5PEEd

. During

configuration hysteresis is shown in the units of 

5PEED

previously configured for the Tachometer display.

Using the  

&

 or  

*

 push button select  

H5tr

 in the

selected  alarm  sub-menu  and  press  

(

 which  will

reveal the existing hysteresis with one digit flashing.
The  required  hysteresis  can  be  entered  using  the

&

 or 

*

 push button to adjust the flashing digit and

the  

(  

button  to  transfer  control  to  the  next  digit.

When set as required press 

)

 to enter the value and

return to the 

H5tr

 prompt in the alarm sub-menu.

e.g.  A Tachometer configured to display a rotational
speed of 0 to 500 RPM, with a high alarm set at   400
RPM  and  hysteresis  of  10  RPM  will  perform  as
follows:

The high alarm will be activated when speed
equals or exceeds 400 RPM, but will not reset
until the speed falls below 390 RPM.

9.4.10  Alarm delay:  

dELA

This function enables activation of the alarm output to
be  delayed  for  a  fixed  time  following  the  alarm
condition occurring.  The delay can be set in 1 second
increments  up  to  3600  seconds.    If  a  delay  is  not
required zero should be entered.

To adjust the delay select  

dELA

 using the  

&

 or 

*

push  button  in  the  selected  alarm  sub-menu  and
press  

(  

which will reveal the existing delay time in

seconds with one digit flashing.  The required delay
time can be entered using the  

&

 or 

*

 push button

to  adjust  the  flashing  digit  and  the  

(  

button  to

transfer  control  to  the  next  digit.      When  set  as
required press 

to enter the value and return to the

dELA

  prompt  in  the  alarm  sub-menu.    The  alarm

annunciator  will  start  flashing  immediately  an  alarm
condition occurs and will continue for the delay time,
after which the alarm output will be activated and the
alarm annunciator will be permanently activated.

9.4.11  Alarm silence time:  

5IL

The  alarm  silence  function  is  primarily  intended  for
use  in  small  installations  where  the  alarm  output
directly operates an annunciator such as a sounder.
When the alarm silence time is set to any figure other
than  zero,  the  

(  

push  button  becomes  an  alarm

accept button.

After an alarm has occurred, operating the 

(

 button

will cause the alarm output to revert to the non-alarm
condition for the configured alarm silence time.  When
an alarm is silenced the alarm annunciator will flash
until the silence time expires.

To adjust the alarm silence time select 

5iL

 using the

&

 or 

*

  push  button  in  the  selected  alarm  sub-

menu  and press  

(  

which will  reveal  the existing

alarm silence time in seconds with one digit flashing.
The required delay time can be entered using the

&

 or 

*

 push button to adjust the flashing digit and

the  

(

 button to transfer control to the next digit.

When set as required press  

)  

to enter the value

and return to the 

5iL

 prompt in the alarm sub-menu.

9.4.12  Flash display when alarm occurs:  

FL5H

In  addition  to  the  two  alarm  annunciators  at  the
bottom  left  hand  side  of  the  Tachometer  display
which show the status of both alarms, this function
provides an even more conspicuous indication that
an alarm condition has occurred.

When enabled, this function alternates the speed or
run-time  display  between  the  numerical  value  and
the alarm identification AL1 or AL2 when an alarm
occurs.

Using the 

&

 or 

*

 push button select 

FL5H

 from the

selected alarm sub-menu and press 

to check or

change the function.  The 

&

 or 

*

 push button will

toggle the function between 

oFF

 and 

on

, when set as

required, press the  

)  

button to return to the  

FL5H

prompt in the alarm sub-menu.

9.4.13  Access Setpoint:  

AC5P

This  function  activates  a  separate  menu  that
provides direct access to the alarm setpoints when
the  Tachometer  is  in  the  display  mode  by
simultaneously  operating  the  

(

 and 

*

 buttons.

An operator can therefore adjust the alarm setpoints
without having access to the configuration and alarm
sub-menus.    Protection  against  unauthorised  or
accidental  adjustment  is  provided  by  a  separate
security access code.  

Using the 

&

 or 

*

 push button select 

AC5P

 from the

configuration  menu  and  press  

(  

to  reach  the

enable  function  

EnbL

.  Pressing  

(  

will  reveal  the

existing  setting  which  can  be  toggled  between  

on

and  

oFF

 by  pressing  the  

&

 or 

*

 push  button.

When set as required, press the 

button to return

to the  

EnbL

 prompt from which a separate security

access code can be entered using the 

ACCd

 function

which  can  be  selected  using  the  

or

 *

 push

button.

To enter a new security code select  

ACCd

 from the

sub-menu  and  press  

(

  which   will   cause   the

Tachometer to display  

0000

 with one digit flashing.

The  flashing  digit  may  be  adjusted  using  the

&

 and 

*

  push  button,  when  set  as  required

operating the  

(  

button will transfer control to the

next digit.   When all the digits have been adjusted
press 

to return to the 

ACCd

 prompt.

31

Summary of Contents for BA317NE

Page 1: ...Issue 7 9th July 2019 BA317NE Rugged one input Ex nA and Ex tc Tachometer Issue 7...

Page 2: ...tion functions 6 4 Input inPut 6 5 Input type inP tYPE 6 6 Debounce dEbouncE 6 7 Display update interval uPdAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale facto...

Page 3: ...Adjusting alarm setpoints from display mode 9 5 Pulse Output 9 5 1 Ex nA certification 9 5 2 Pulse output configuration 9 5 3 Enable pulse output EnbL 9 5 4 Source of output pulse 5ourCE 9 5 5 Divide...

Page 4: ...4...

Page 5: ...n Appendix 2 For applications in the USA and Canada the BA317NE has ETL and cETL certification which is described in Appendix 3 2 OPERATION Fig 1 shows a simplified block diagram of the BA317NE Tachom...

Page 6: ...displays and associated annunciators plus a pulse input indicator as shown on front cover of this manual Speed On upper eight digit display display Run time On lower six digit display display Shows t...

Page 7: ...or an external Zener barrier or galvanic isolator as shown on the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure lo...

Page 8: ...BA317NE Certification information label 4 SYSTEM DESIGN FOR HAZARDOUS AREAS When correctly installed in Zone 2 the BA317NE Totaliser may be connected to almost any apparatus in the safe area and to Ex...

Page 9: ...ation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered nec...

Page 10: ...A317NE contains a configurable debounce circuit to prevent false triggering See section 6 7 4 2 5 Magnetic pick off input Magnetic pick off speed sensors usually have a low level ac voltage output whi...

Page 11: ...osure Ensure that the edges of aperture are de burred b Inspect the Tachometer s captive gasket and ensure that it is not damaged before inserting it into the panel enclosure aperture c If the enclosu...

Page 12: ...showing the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units...

Page 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time clock that displays the time in hours that the speed of the monito...

Page 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 16: ...16...

Page 17: ...17...

Page 18: ...ch as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that has be...

Page 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Page 21: ...is displayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button...

Page 22: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Page 23: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 24: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Page 25: ...ng calibration change Re enable both alarms 8 2 Fault finding after commissioning BS EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analys...

Page 26: ...output 2 or Isolated dual alarms 2 Notes 1 Internally powered 2 Only one of the three output options can be fitted to a BA317NE Tachometer 9 1 Scale card The BA317NE has a window on the right hand sid...

Page 27: ...ons such as a shut down system When the BA317NE Tachometer power supply is turned off or disconnected the alarm outputs will open irrespective of whether normally open or normally closed outputs have...

Page 28: ...ve use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered necessary to have a means of isolation...

Page 29: ...ust therefore be reconfigured before use 9 4 6 Setpoint adjustment 5P1 x 5P2 x The speed alarm setpoints 5P1 5peed and 5P2 5peed may be positioned anywhere between 0000000 and 9999999 and the run time...

Page 30: ...30...

Page 31: ...the configured alarm silence time When an alarm is silenced the alarm annunciator will flash until the silence time expires To adjust the alarm silence time select 5iL using the or push button in the...

Page 32: ...digit using the or buttons to adjust the flashing digit and the push button to move control to the next digit If the correct code is entered pressing will then cause alarm setpoint prompt 5P1 5peed o...

Page 33: ...ned The retransmitted RTx annunciator on the instrument display shows the status of the retransmitted pulse output Annunciator activation depends upon the setting of 5ource in the pulse output configu...

Page 34: ...e standard 9 5 2 Pulse output configuration PuL5E oP When the BA317NE Tachometer is supplied with a factory fitted pulse output the configuration menu is extended as shown in Fig 18 to include the pul...

Page 35: ...changed by pressing the or push button followed by the button to return to 5ourCE prompt 9 5 5 Divide output pulse frequency diVidE When 5CALEd is selected in the 5ourCE function described in section...

Page 36: ...20mA output to be connected to any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V dc Providing that the BA317NE Tachometer is correctly installed in a...

Page 37: ...ponds to a 4 000mA output current is defined by this function Using the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing...

Page 38: ...afe use in dust atmospheres The BA317NE ATEX Type Examination Certificate has an X suffix to show that special conditions for safe use are specified by the BA317NE Ex ic tc certificate indicated by th...

Page 39: ...for an external Zener barrier or galvanic isolator as shown on the IECEx Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure located in...

Page 40: ...parameters the systems shown in sections 3 4 and 5 of this manual may therefore also be used for US and Canadian installations subject to complying with local codes of practice ETL and cETL codes CL...

Reviews: