background image

24

9.4.4  Alarm enable:  ‘EnbL’

This function allows each alarm to be enabled or
disabled  without  altering  any  of  the  alarm
parameters. To enable or disable the alarm select
'EnbL' from the alarm menu and press 

P

 which will

reveal  the  current  setting  ‘on’  or  ‘oFF’.    The
function can be changed by pressing the 

 or 

button  followed  by  the  

E

 button  to  return  to  the

alarm menu.

9.4.5  Setpoint adjustment:   ‘SP1’ and ‘SP2’

The  setpoint  of  each  alarm  may  be  positioned
anywhere in the numerical display of the indicator
providing that this corresponds to an input current
between 3.8 and 20.2mA. e.g. If the indicator has
been calibrated  to display 0 with 4mA input and
10000  with  20mA input,  the  two  alarm  setpoints
may be positioned anywhere between  -125 and
10125.  
To adjust the setpoint select 'SP1' or 'SP2' from the
alarm configuration menu and press  

P

 

which will

reveal  the  existing  alarm  setpoint.    The  flashing
digit of the setpoint can be adjusted using the 

and 

 push  buttons, and  the  

P

 button  to  move

control  to  the  next  digit.    When  the  required
setpoint has been entered press 

E

 

to return to the

alarm configuration menu.
The alarm setpoints may also be adjusted when
the indicator is in the display mode, see section
9.4.12.

9.4.6  Alarm function:   ‘Hi.Lo’

Each alarm can be independently conditioned as a
high alarm or as a low alarm.   To check or change
the  alarm  function  select  'Hi.Lo'  from  the  alarm
menu  and  press  

P

 to  reveal  the  current  setting.

The function can be changed by pressing the 

 or

 button followed by the 

E

 button to return to the

alarm menu.

9.4.7  Alarm output status:   ‘no.nC’

Configures the solid state alarm output to be open
‘no’ or to be closed ‘nC’ in the non-alarm condition.
When deciding which is required, care should be
taken to ensure that the alarm output is fail safe as
illustrated in Fig 9.

‘no’ Alarm output open in non-alarm condition

‘nC’ Alarm output closed in non-alarm condition

CAUTION

When the 4/20mA supply is removed from the
loop  powered  indicator,  both  alarm  outputs
will  open  irrespective  of  conditioning.
Therefore for fail  safe  operation  both alarm
outputs should be conditioned to be open in
the alarm condition ‘nC’.

To check or change the alarm output status, select
'no.nC'  from  the  alarm  configuration  menu  and
press 

P

 to reveal the setting.  The function may be

changed by pressing the 

 or 

 button followed

by the 

E

 

button to return to the alarm configuration

menu.

9.4.8  Hysteresis:   HStr

Hysteresis is shown in the units that the indicator
has been calibrated to display.
To  adjust  the  hysteresis  select  'HStr'  from  the
alarm  menu  and  press  

P

  which  will  reveal  the

existing figure.  The flashing  digit can be adjusted
using  the  

 and  

 push  buttons,  and  the  

P

button will move control to the next digit.  When the
required  hystersis  has  been  entered  press  

E

 

to

return to the alarm configuration menu.

e.g.  An indicator calibrated to display 0 to 10000,
with a high alarm set at 9000 and hysteresis of 200
will perform as follows:

The  high  alarm  will  be  activated  when
increasing indicator display equals 9000, but
will not reset until the indicator display falls
below 8800.

9.4.9  Alarm delay:   dELA

This function delays activation of the alarm output
for an adjustable time following the alarm condition
occurring.    The  delay  can  be  set  in  1  second
increments   between   0   and   3600   seconds.     If   a
delay is not required zero should be entered.  To
adjust  the  delay  select  'dELA'  from  the  alarm
configuration menu and press  

P

 which will reveal

the existing delay.  The flashing digit of the delay
can be adjusted using the 

 and 

 push buttons,

and the 

P

 button to move control to the other digits.

When the required delay has been entered press

E

 

to return to the alarm menu.

e.g.  An indicator with a high alarm set at 9000 and
an  alarm  delay  of  30  seconds  will  perform  as
follows:

The alarm annunciator will start to flash when an
increasing indicator display equals 9000, but the
alarm output will not be activated until the alarm
condition has existed continuously for 30 seconds.
When  the  alarm  output  is  activated,  the  alarm
annunciator  will  stop  flashing  and  become
permanently activated.

If the ‘FLSH’ function, which flashes the indicator
display when an alarm occurs, has been enabled,
it will not start to function until the alarm output is
activated.   
See section 9.4.11

Summary of Contents for BA307NE

Page 1: ...Issue 3 1st Novemeber 2017 BA307NE BA327NE Ex nA Ex tc loop powered panel mounting indicators Issue 3...

Page 2: ...figuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Scale...

Page 3: ...European ATEX Directive 94 9 EC The certificate number has an X suffix indicating that the two indicators are subject to special condition for safe use For installations in Zone 2 the panel enclosure...

Page 4: ...both instruments with a common Type Examination Certificate number ITS14ATEX48028X This has been used to confirm compliance with the European ATEX Directive for Group II Category 3GD equipment The in...

Page 5: ...roups Group A propane Group B ethylene Group C hydrogen In gases that may safely be used with equipment having a temperature classification of T1 450o C T2 300o C T3 200o C T4 135o C T5 100o C At ambi...

Page 6: ...ea should be individually fused and contain a means of isolation These two requirements are frequently satisfied by using switch fuse holders with easily removable fuses which can be extracted to achi...

Page 7: ...is a satisfactory method at the low voltages and currents common in instrumentation systems Clear identification of and easy access to the means of isolation is essential for their effective use It i...

Page 8: ...el enclosure cut out dimensions Fig 4 Dimensions 5 2 Installation Procedure a Cut the aperture specified in Fig 4 in the panel enclosure Ensure that the edges of aperture are de burred b Inspect the i...

Page 9: ...ard showing the requested units of measurement if this information is not supplied when the indicator is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common uni...

Page 10: ...10...

Page 11: ...uration BA307NE BA327NE Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00...

Page 12: ...in 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pr...

Page 13: ...tween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the i...

Page 14: ...rompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access New instruments...

Page 15: ...e This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this me...

Page 16: ...16...

Page 17: ...to the required value before the P button is operated to enter the required indicator display Error message If during calibration the indicator displays a FAiL error message the current at which the s...

Page 18: ...oints has been defined and then return to the in sub function by pressing the E button The corresponding indicator display at each of the break points can now be defined using the diSP sub function Us...

Page 19: ...rior of the instrument with dust or moisture Some end users may prefer not to permit live maintenance to minimise risk ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance within the hazar...

Page 20: ...the enclosure panel being distorted or creeping when the indicator panel clamps are tightened and ensures that the joint between the indicator and the panel enclosure in which it is mounted remains se...

Page 21: ...ed in Zone 2 is displaying the output from an Flameproof Ex d 2 wire transmitter located in Zone 1 Alarm 1 is switching an Ex e sounder in Zone 1 and alarm 2 is switching a sounder located in the safe...

Page 22: ...22...

Page 23: ...ndicator display equals the setpoint See section 9 4 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 4 6 no nC Normally open or normally closed output Sets the alarm out...

Page 24: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 25: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 26: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 16 Fig 16 Displayed value and setpoints on bargra...

Page 27: ...o or greater than 9V At lower supply voltages the backlight will continue to function but with reduced brilliance and will draw less current The ATEX certificate therefore only specifies the maximum s...

Page 28: ...re four design requirements 1 The indicator should be installed generally as shown in section 5 and Fig 20 2 The certificate specifies that the indicator should be connected to a limited energy 4 20mA...

Page 29: ...Fig 21 2 The four vents at the rear of the indicator enclosure shown in Fig 22 must not be obstructed 3 The certificate specifies that the indicator should be connected to a limited energy 4 20mA circ...

Page 30: ...ne 22 The panel enclosure containing the indicator should be located where the minimum amount of dust will accumulate on them and the installation should be as specified in section 5 of this instructi...

Page 31: ...X 4 ETL cETL certification for installations in USA and Canada A4 0 cETL Mark For installations in the USA and Canada the BA307NE and BA327NE indicators have ETL and cETL Ex nA and Ex tc approval Cont...

Reviews: