background image

20

9.  ACCESSORIES

9.1  Scale card

Both models have a window on the right hand side
of the display through which to view a scale card
showing  the  units  of  measurement  such  as  

o

C,

mBar or RPM.   New indicators are fitted with a
scale  card  showing  the  units  of  measurement
specified  when  the  indicator  was  ordered,  if  the
units are not specified a blank scale card will be
fitted.      A pack  of  scale  cards  pre-printed  with
common units of measurement is available as an
accessory.    These  can  easily  be  fitted  to  the
indicator  on-site  without  opening  the  indicator
enclosure or removing it from the panel enclosure.
See section 5.5 of this instruction manual.   

Less common units of measrement can be hand
printed  onto  the  scale  card  using  a  variety  of
techniques, or custom printed cards are available
from BEKA.  

9.2  Tag information

New  indicators  can  be  supplied  with  tag  or
application information laser etched onto the rear
of  the  instrument.    This  tag  information  is  not
visible  from  the  front  of  the  instrument  after
installation.  

9.3  Stainless steel support plate

When  a  BA307NE  or  BA327NE  indicator  is
installed  into  an  enclosure panel  less  than  1mm
thick  or  in  a  non-metallic  enclosure  panel,  a
support  plate  may  be  required  as  explained  in
section 5.2c of this manual.    This plate prevents
the  enclosure  panel  being  distorted  or  creeping
when the indicator panel clamps are tightened and
ensures that the joint between the indicator and the
panel  enclosure  in  which  it  is  mounted  remains
sealed.

9.4  Alarms

CAUTION

These alarms outputs should not be used for
critical  safety  applications  such  as  an
emergency shut down system.

Both  models  can  be  supplied  with  factory  fitted
dual solid state, single pole alarm outputs.   Each
alarm output may be independently conditioned as
a  high  or  low  alarm  with  a  normally  open  or
normally closed output in the non-alarm condition.  

When the 4/20mA current powering the indicator is
removed both alarm outputs will open irrespective
of configuration.  The open circuit condition should
therefore be chosen as the alarm condition when
designing an alarm system.    Fig 11 illustrates the
conditions available and shows which are fail safe. 

When an  alarm  occurs  an  alarm  annunciator  on
the  indicator's  front  panel  is  activated  and  if
required  the  numerical  display  can  alternate
between  the  measured  value  and  the  alarm
channel identification ‘ALr1’ or ‘ALr2’.

CAUTION

The  alarms  are  activated  by  the  indicator’s
numerical display.  Use of the Tare Function
‘tArE’ will change the numerical  display, the
alarms will continue to function at the original
displayed value, but this will correspond to a
different input current.

Fig 11  Alarm outputs

Configurable  functions  for  each  alarm  include
adjustable  setpoint,  hysteresis,  alarm  delay  and
alarm accept.

Summary of Contents for BA307NE

Page 1: ...Issue 3 1st Novemeber 2017 BA307NE BA327NE Ex nA Ex tc loop powered panel mounting indicators Issue 3...

Page 2: ...figuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Scale...

Page 3: ...European ATEX Directive 94 9 EC The certificate number has an X suffix indicating that the two indicators are subject to special condition for safe use For installations in Zone 2 the panel enclosure...

Page 4: ...both instruments with a common Type Examination Certificate number ITS14ATEX48028X This has been used to confirm compliance with the European ATEX Directive for Group II Category 3GD equipment The in...

Page 5: ...roups Group A propane Group B ethylene Group C hydrogen In gases that may safely be used with equipment having a temperature classification of T1 450o C T2 300o C T3 200o C T4 135o C T5 100o C At ambi...

Page 6: ...ea should be individually fused and contain a means of isolation These two requirements are frequently satisfied by using switch fuse holders with easily removable fuses which can be extracted to achi...

Page 7: ...is a satisfactory method at the low voltages and currents common in instrumentation systems Clear identification of and easy access to the means of isolation is essential for their effective use It i...

Page 8: ...el enclosure cut out dimensions Fig 4 Dimensions 5 2 Installation Procedure a Cut the aperture specified in Fig 4 in the panel enclosure Ensure that the edges of aperture are de burred b Inspect the i...

Page 9: ...ard showing the requested units of measurement if this information is not supplied when the indicator is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common uni...

Page 10: ...10...

Page 11: ...uration BA307NE BA327NE Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00...

Page 12: ...in 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pr...

Page 13: ...tween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the i...

Page 14: ...rompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access New instruments...

Page 15: ...e This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this me...

Page 16: ...16...

Page 17: ...to the required value before the P button is operated to enter the required indicator display Error message If during calibration the indicator displays a FAiL error message the current at which the s...

Page 18: ...oints has been defined and then return to the in sub function by pressing the E button The corresponding indicator display at each of the break points can now be defined using the diSP sub function Us...

Page 19: ...rior of the instrument with dust or moisture Some end users may prefer not to permit live maintenance to minimise risk ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance within the hazar...

Page 20: ...the enclosure panel being distorted or creeping when the indicator panel clamps are tightened and ensures that the joint between the indicator and the panel enclosure in which it is mounted remains se...

Page 21: ...ed in Zone 2 is displaying the output from an Flameproof Ex d 2 wire transmitter located in Zone 1 Alarm 1 is switching an Ex e sounder in Zone 1 and alarm 2 is switching a sounder located in the safe...

Page 22: ...22...

Page 23: ...ndicator display equals the setpoint See section 9 4 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 4 6 no nC Normally open or normally closed output Sets the alarm out...

Page 24: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 25: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 26: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 16 Fig 16 Displayed value and setpoints on bargra...

Page 27: ...o or greater than 9V At lower supply voltages the backlight will continue to function but with reduced brilliance and will draw less current The ATEX certificate therefore only specifies the maximum s...

Page 28: ...re four design requirements 1 The indicator should be installed generally as shown in section 5 and Fig 20 2 The certificate specifies that the indicator should be connected to a limited energy 4 20mA...

Page 29: ...Fig 21 2 The four vents at the rear of the indicator enclosure shown in Fig 22 must not be obstructed 3 The certificate specifies that the indicator should be connected to a limited energy 4 20mA circ...

Page 30: ...ne 22 The panel enclosure containing the indicator should be located where the minimum amount of dust will accumulate on them and the installation should be as specified in section 5 of this instructi...

Page 31: ...X 4 ETL cETL certification for installations in USA and Canada A4 0 cETL Mark For installations in the USA and Canada the BA307NE and BA327NE indicators have ETL and cETL Ex nA and Ex tc approval Cont...

Reviews: