1.  DESCRIPTION

The BA307C and BA308C are intrinsically safe
loop powered 3½ digit indicators that display the
current flowing in a 4/20mA loop in engineering
units.  Both instruments introduce less than a 1.1V
drop which allows them to be installed into almost
any 4/20mA current loop.  No additional power
supply or battery is required.

The two indicators are electrically similar, but have
different size displays and enclosures.

 

 Model    Display height    Bezel size

BA307C

12.7mm

96 x 48mm

BA308C

25.4mm

144 x 72mm

The main application of the BA307C and BA308C
is to display a measured variable or control signal
in a hazardous process area.  The zero and span
of the display are independently adjustable so that
the indicators can be calibrated to display any
variable represented by the 4/20mA current, e.g.
temperature, flow, pressure or level.

The BA307C and BA308C have been certified
intrinsically safe for use in gas hazardous areas by
Notified Body Intertek Testing and Certification Ltd
which has been used to confirm compliance with
the European ATEX Directive 94/9/EC.       The
EC-Type Examination certificate specifies that
under fault conditions the output voltage, current
and power at the 4/20mA input terminals will not
exceed those specified for 

simple apparatus

 in

Clause 5.7 of EN 60079-11, which simplifies
installation and documentation.

The BA307C and BA308C are also FM approved
for use in the USA and cFM approved for use in
Canada,  these  approvals  are  described  in
Appendix 1.

International IECEx certification is described in
Appendix 2.

2.  OPERATION

Fig 1 shows a simplified block diagram of both
models.  The 4/20mA input current flows through
resistor R1 and forward biased diode D1.  The
voltage developed across D1, which is relatively
constant, is multiplied by a switch mode power
supply and used to power the analogue to digital
converter and liquid crystal display.  The voltage
developed across R1, which is proportional to the
4/20mA input current, provides the input signal for
the analogue to digital converter.

Fig 1 Simplified block diagram of BA307C
         and BA308C

3. INTRINSIC SAFETY CERTIFICATION

3.1 ATEX certificate

The BA307C and BA308C were issued with an
EC-Type Examination Certificate number
ITS02ATEX2027 by Notified Body  ITS Testing and
Certification Ltd.  This confirmed compliance with
European ATEX standards for Group II, Category
1G equipment, EEx ia IIC T5 at the time of
certification.  Please see the BEKA product
Declaration of Conformity for confirmation of
compliance with current harmonised ATEX
standards.  Both indicators carry the Community
Mark and, subject to local codes of practice, may
be installed in any of the European Economic Area
(EEA) member countries.  ATEX certificates are
also acceptable for installations in Switzerland.
This manual describes installations that conform
with EN 60079: Part 14 Electrical Installations
design, selection and erection in hazardous areas.
When designing systems for installation outside
the UK, the local Code of Practice should be
consulted.

Summary of Contents for BA307C

Page 1: ...Issue 9 22nd March 2013 BA307C BA308C Intrinsically safe loop powered 3 digit panel mounting indicators issue 9 ...

Page 2: ... example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 1 Scale card 8 2 Tag strip 8 3 Internal calibrator 8 4 Root extractor 8 4 1 Calibration example 8 5 Display backlights 8 5 1 Separately powered 8 5 2 Loop powered Appendix 1 FM cFM Appr...

Page 3: ... and cFM approved for use in Canada these approvals are described in Appendix 1 International IECEx certification is described in Appendix 2 2 OPERATION Fig 1 shows a simplified block diagram of both models The 4 20mA input current flows through resistor R1 and forward biased diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used ...

Page 4: ... 1G EEx ia IIC T5 apparatus at Tamb 40 to 60o C When connected to a suitable system the instruments may be installed in Zone 0 explosive gas air mixture continuously present Zone 1 explosive gas air mixture likely to occur in normal operation Zone 2 explosive gas air mixture not likely to occur and if it does will only exist for a short time Be used with gases in groups Group A propane Group B eth...

Page 5: ...r BA308C in a transmitter loop 4 2 Remote indication BA307C and BA308C indicators may be driven via an intrinsically safe interface from a 4 20mA safe area signal to provide a remote indication within a hazardous area The type of interface is not critical either a Zener barrier or a galvanic isolator may be used providing that Uo Io and Po are not exceeded If one side of the 4 20mA current loop ma...

Page 6: ... the panel The indicators may be installed in any instrument panel providing the environmental limits shown in the specification are not exceeded Figs 4A and 4B show the overall dimensions of each instrument and the size of the required panel cut out To achieve an IP65 seal between the instrument enclosure and the instrument panel the smaller tolerance aperture should be used and the BA308C must b...

Page 7: ... Figs 4A and 4B To simplify installation the terminals are removable so that the panel wiring can be completed before the instrument is installed Fig 5 Fitting panel mounting clips 5 3 EMC Both instruments comply with the requirements of the European EMC Directive 2004 108 EEC For specified immunity all 4 20mA wiring should be in screened twisted pairs with the screen earthed within the safe area ...

Page 8: ...uld be calibrated using an external traceable current source with an accuracy greater than 4 A However when verification is not required the indicator can be fitted with an optional internal calibrator which allows rapid calibration without the need for external instruments See section 8 3 for details 6 1 Zero adjustment Zero is defined as the number displayed by the indicator with a 4 000mA input...

Page 9: ...play 25 0 with a 4 000mA input 115 0 with a 20 000mA input i e A zero of positive 250 Ignoring A span of 900 decimal point A decimal point in position 00 0 The following adjustments are required Step 1 The BA307C is required to display a positive zero therefore the suppression elevation links should be put in the elevation position Step 2 The required zero is 250 therefore the zero link should be ...

Page 10: ...aintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA307C or BA308C fails after it has been functioning correctly the following procedure should be followed Symptom Cause Solution No display and 0V between terminals 1 and 3 No power supply Check that a current is...

Page 11: ...umber is not visible from the front of the instrument after installation 8 3 Internal Calibrator Both indicators can be supplied with an optional internal calibrator which simulates 4 and 20mA input currents This allows rapid calibration without the need for external instruments or disconnection from the 4 20mA input current but it is not a substitute for calibration with a traceable external curr...

Page 12: ...instrument with an internal calibrator Fig 9 Location of clip off link 8 4 1 Calibration example with root extractor The indicator is required to display rate of flow in gallons per minute with a resolution of 0 1 gallons The differential flowmeter has an output of 20mA at a flow rate of 140 0 gallons per minute i e A span of 1400 ignoring the decimal point A decimal point in position 00 0 The fol...

Page 13: ...Certificate specifies that the maximum equivalent capacitance and inductance between terminals 12 and 13 is Ci 0 045µF Li 0 02mH To determine the maximum permitted cable parameters these figures should be subtracted from the maximum permitted cable capacitance and inductance specified by the certificate for the Zener barrier or galvanic isolator powering the backlight Fig 10 Backlight power supply...

Page 14: ... thus significantly reducing the installation cost A shown in Fig 11 the backlight may be connected in series with the indicator Any Zener barrier or galvanic isolator certified EEx ia IIC by a European Notified Body may be used providing the output parameters do not exceed Uo 30V dc Io 200mA Po 0 85W Fig 11 Loop powered backlight Connecting the backlight in series with the indicator will increase...

Page 15: ...8C have a T4 rating at ambient temperatures between 20o C and 60o C and may be used in the following divisions with the following gases Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D The FM entity parameters are similar to the ATEX parameters The intrinsically safe circuits shown in this manual may therefore be used for installations in the USA providing the Zener barriers and ...

Page 16: ...16 ...

Page 17: ...17 ...

Page 18: ...18 ...

Page 19: ... Conformity number IECEx ITS 05 0002 which specifies the following certification code and marking Ex ia IIC T5 Ta 40o C to 60 o C The specified intrinsic safety parameters are identical to the ATEX safety parameters The IECEx certificate may be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A2 2 Installation The IECEx and ATEX certificates specify identical sa...