Setpoints Dialog Box
Parameters
The Parameters dialog allows the user to select
desired voltage values for regulation during ini-
tialization of the tap changer control.
Forward power Bandcenter is adjustable from
90.0 V to 135.0 V in 0.1 increments with a facto-
ry setting of 120 V.
Volt Reduction is currently unavailable, and will
appear greyed-out in display.
Two voltage limits, each adjustable from 89 V to
135 V in 1 V increments for the Lower Voltage
Limit, and 90 to 136 V in 1 V increments for the
Upper Voltage Limit. The Volt Upper Limit is
factory set at 132 V. The Volt Lower Limit is
factory set at 108 V.
VT User Corr voltage is adjustable from
–12 V to +12 V in 0.01 increments, with a factory
setting of 0.00 V.
VT Ratio Multiplier adjustable from 20 to 5000
in 1 increments, with a factory setting of 60.
CT User Corr multiplier is adjustable from 50%
to 200% in 1% increments, with a factory setting
of 100%.
CT Multiplier adjustable from 20 to 25,000 in 1
increments with a factory setting of 60.
CT Phasing correction is adjustable from 0° to 330°
in 30° increments with a factory setting of 0°.
VRQF is adjustable from 0.4 V to 2.0 V in 0.1 V
increments.
History Samples: 5–60 minutes, at 1 minute in-
crements, with a default setting of 5.0 minutes.
Summary of Contents for M-2601
Page 1: ...Instruction Book M 2601 02 03 Autodaptive Regulator Control ...
Page 21: ...This Page Left Intentionally Blank ...
Page 47: ...5 2 M 2601 02 03 Instruction Book This Page Intentionally Left Blank ...
Page 65: ...1 3 A B C 7 14 M 2601 02 03 Instruction Book This Page Left Intentionally Blank ...
Page 67: ...M 2601 02 03 Instruction Book A 2 This Page Left Intentionally Blank ...