Technical data, mounting, wiring
PS1061-2410-0000
22
Version: 1.0
3.12
EMC
The device allows use in the industrial sector.
The device was developed in accordance with EN 61000-6-1, EN 61000-6-2, EN 61000-6-4 and EN
61000-3-3.
This device complies with the provisions of FCC Part 15. Operation is subject to the two following conditions:
1. This device must not cause harmful interference and
2. this device must accept all interference received, including interference that may cause unwanted op-
eration.
Without additional measures to reduce harmonics on the input side (PFC), the power supply is not suitable
for connection to the public supply grid in residential, business and commercial areas or in small businesses.
The power supply can be operated without further measures in the industrial sector. There are exceptions for
various countries outside of the European Union and these must be determined locally.
The device is unsuitable for AC 200 V mains supplies and more than 8 A load current, if a short drop in the
output voltage in case of mains interruptions (even with interruptions shorter than 20 ms) is incompatible with
the application.
EMC interference immu-
nity
Strong transients
VDE 0160 Over the entire load range
750 V, 1.3 ms
EMC interference emis-
sion
According to the generic standards: EN 6100-6-3 and EN6100-6-4
Conducted interference
emission, input lines
EN 55011, EN 55022, FCC Part 15,
CISPR 11, CISPR 22
Class B
Conducted interference
emission, output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Limit values for local DC networks not
fulfilled
Interfering radiation
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
not met
Voltage fluctuations, flicker EN 61000-3-3
Fulfilled, tested with constant current
loads, non-pulsing
Switching frequencies
Main converter
75 to 120 kHz
Dependent on output voltage and
load