Technical data, mounting, wiring
PS1061-2410-0000
20
Version: 1.0
3.9
Terminals and wiring
The terminals are designed to be finger-safe according to IP20 and are suitable for field or factory wiring.
Technical data
Input
Output
DC-OK signal
Connection cross-section
e*: max. 6 mm²
f*: max. 4 mm²
a*: max. 4 mm²
(d<2.8 mm)
e*: max. 6 mm²
f*: max. 4 mm²
a*: max 4 mm²
(d<2.8 mm)
e*: max. 1.5 mm²
f*: max. 1.5 mm²
a*: max. 1.5 mm²
(d<1.6 mm)
Connection cross section
(AWG)
e*: AWG 20-10
f*: AWG 20-10
a* AWG 20-10 (d<2.8 mm)
e*: AWG 20-10
f*: AWG 20-10
a* AWG 20-10
(d<2.8 mm)
e*: AWG 24-16
f*: AWG 24-16
a*: AWG 24-16
(d<1.6 mm)
Strip length
7 mm / 0.28 inch
7 mm / 0.28 inch
7 mm / 0.28 inch
e* = solid wire
f* = stranded wire
a* = with ferrule
Wiring instructions:
• Use suitable copper cables that are designed for at least the following operating temperatures:
+75 °C, for ambient temperatures up to +55 °C (minimum) and
+90 °C, for ambient temperatures up to +70 °C (minimum)
• Observe the national installation rules and regulations!
• Do not use the device without PE connection.
• Make sure that all single wires of a strand are connected to the terminal!
• Unused terminals should be tightened firmly.
• Ferrules are permitted.
3.10
Functional wiring diagram
Fig. 8: Functional wiring diagram