Technical data, mounting, wiring
PS1061-2410-0000
14
Version: 1.0
3.3
Input inrush current
An NTC input inrush current limiter, which is bridged by a relay contact in normal operation, limits the input
inrush current after the input voltage is switched on.
The charge current of the interference suppression capacitors during the first few microseconds after
switching on is not taken into account.
AC 230 V
Input inrush current
Max.
59 A
peak
At +40 °C, cold start
Typ.
48 A
peak
At +40 °C, cold start
Typ.
35 A
peak
At +25 °C, cold start
Inrush energy
Max.
2.5 A
2
s
At +40 °C, cold start
Fig. 3: Input inrush current surge, typical behavior 230 Vac input, 24 V 10 A output, 25 °C ambient
temperature;
Input inrush current, zoomed in to the first peak, 230 Vac input, 24 V 10 A output, 25 °C ambient temperature