Technical data, mounting, wiring
PS1061-2410-0000
15
Version: 1.0
3.4
Output
The output provides an SELV/PELV nominal voltage that is electrically isolated from the input voltage.
The output is designed to supply any type of load, including capacitive and inductive loads.
The output is electronically protected against overload, no-load and short circuit. Noise may be audible in the
case of a protective event.
Output
Output voltage
Nom.
DC 24 V
Adjustment range
Min.
24 - 28 V
Guaranteed value
Max.
30 V
1)
In end position of the potentiometer, clockwise.
Factory settings
Typ.
24.1 V
±0.2 %, under full load and cold device
Line regulation
Max.
50 mV
85 - 300 Vac
Load regulation
Max.
150 mV
0 A → 10 A, static value, see fig.
Output voltage over output current, typical
Residual ripple and ripple
voltage
Max.
100 mVpp 20 Hz to 20 MHz, 50 Ohm
Output current
2)
Nom.
10 A
At 24 V and ambient temperature below 55 °C
Nom.
8.6 A
At 28 V and ambient temperature below 55 °C,
Nom.
6.25 A
At 24 V and an ambient temperature of 70 °C
Nom.
5.4 A
At 28 V and an ambient temperature of 70 °C
Overload characteristics
Continuous cur-
rent
see Fig.
Output voltage over output current, typ.
Overload/short circuit
current
Max.
16 A
Continuous current, load impedance 50 mOhm, see Fig.
Output voltage over output cur-
rent, typ.
Output capacity
Typ.
4,400 µF
Included in the power supply
Back-feeding loads
Max.
35 V
This power supply is stable and will not malfunction if a load is feeding back voltage to
the power supply. It is irrelevant whether the power supply is switched on or off. The ab-
sorbent energy can be calculated according to the large built-in output capacitor.
1)
This is the maximum output voltage that can occur in the end position of the potentiometer in clockwise direction due to tolerances. It
is not a guaranteed value that can be achieved.
2)
Linear derating b55 °C and 70 °C ambient temperature