KS2000 Configuration Software
KL3444, KL3448, KL3454 und KL3458
38
Version: 3.2.0
•
Watchdog timer active (
)
You can deactivate the watchdog timer here (default: enabled).
•
Signed amount representation (
)
Here you can enable the signed amount representation (default: disabled).
•
Siemens output format (
You can activate Siemens output format here (default: disabled).
•
Overrange protection active (
You can deactivate the overrange protection here (default: enabled).
•
)
You can activate the threshold 1 here (default: disabled).
•
)
You can activate the threshold 2 here (default: disabled).
•
You can deactivate the digital IIR filter (first order) here (default: enabled).
Register values
•
User offset (
)
You can specify the user offset here.
•
User gain (
)
You can specify the user gain here.
•
)
You can specify threshold 1 here.
•
)
You can specify threshold 2 here.
•
IIR filter cut-off frequency (
You can specify the cut-off frequency for the digital IIR filter here.
◦ KL3444, KL3454: default 200 Hz
◦ KL3448, KL3458: default 100 Hz