Access from the User Program
KL3444, KL3448, KL3454 und KL3458
52
Version: 3.2.0
•
R32: Feature register
The feature register specifies the terminal's configuration. Default: 0x0906 (2310
dec
)
Bit
R32.15
R32.14
R32.13
R32.12
R32.11
R32.10
R32.9
R32.8
Name
-
-
-
-
enIIR
enLimit2
enLimit1
enOvRP
Bit
R32.7
R32.6
R32.5
R32.4
R32.3
R32.2
R32.1
R32.0
Name
-
-
-
enSiemens
enSignRepr
enWdTimer
enManScal
enUsrScal
Key
Bit
Name
Description
Default
R32.15
-
reserved
0
bin
...
...
...
...
R32.12
-
reserved
0
bin
R32.11
enIIR
0
bin
digital IIR filter not active
1
bin
1
bin
digital IIR filter active
R32.10
enLimit2
0
bin
Threshold 2 not active
0
bin
1
bin
Threshold 2 active
R32.9
enLimit1
0
bin
Threshold 1 not active
0
bin
1
bin
Threshold 1 active
R32.8
enOvRP
0
bin
Overrange protection is not active
1
bin
1
bin
Overrange protection is active:
If the limit values of registers OvRL (R21) and UnRL (R22) are exceeded, the associated
status bits are set and the measuring range is restricted accordingly.
R32.7
-
reserved
0
bin
R32.6
-
reserved
0
bin
R32.5
-
reserved
0
bin
R32.4
enSiemens
0
bin
Standard output format
0
bin
1
bin
Siemens output format
The three bits with the lowest value are used for displaying status information (see be-
low).
R32.3
enSignRepr
0
bin
Two's complement representation is active
0
bin
1
bin
Signed amount representation is active (-1
dec
= 0x8001)
R32.2
enWdTimer
0
bin
Watchdog timer is not active
1
bin
1
bin
Watchdog timer is active (the watchdog is triggered if no process data are received for
100 ms)
R32.1
enManScal
0
bin
Manufacturer scaling is active
1
bin
1
bin
Manufacturer scaling is not active
R32.0
enUsrScal
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
Siemens output format
If the Siemens output format is selected, the lowest three bits are used for status evaluation. The process
data is represented in bits 15 to 3, with bit 15 representing the sign bit. Scaling of the measured value
according to the Siemens standard has to be done via user scaling (R33, R34).
KL3444
Measured value
Bit 15 ... 3
Bit 2
X
Bit 1
Error
Bit 0
Overflow
Measured value < 20 mA
Process data
0
0
0
Measured value > 20 mA
-
0
0
1
KL3454
Measured value
Bit 15 ... 3
Bit 2
X
Bit 1
wire breakage
Bit 0
under-/overflow
Measured value < 4 mA
-
0
1
1
4 mA <measured value <20 mA
Process data
0
0
0
Measured value > 20 mA
-
0
0
1
Summary of Contents for KL3444
Page 2: ......