KL3448, KL3458 - Product Overview
KL3444, KL3448, KL3454 und KL3458
16
Version: 3.2.0
3.2
Technical Data
Technical Data
KL3448-0000, KS3448-0000
KL3458-0000, KS3458-0000
Number of inputs
8
8
Signal voltage
0 ... 20 mA
4 ... 20 mA
Internal resistance
< 85 Ω
Common-mode voltage U
CM
max. 30 V
max. 30 V
Resolution
12 Bit
Conversion time
approx. 4 ms
Measuring error (total measuring range)
< ±0.3% of the full scale value
Surge voltage resistance
30 V
DC
Electrical isolation
500 V (K-Bus/signal voltage)
Power supply for the electronics
via the K-bus
Current consumption from the K-bus
typically 105 mA
Bit width in process image
Input: 8 x 16 bit user data, 8 x 8 bit control/status (optional)
Weight
approx. 55 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm
Assembly
on 35 mm mounting rail conforms to EN 60715
Pluggable wiring
for all KSxxxx terminals
Permissible ambient temperature range
during operation
0 °C ... + 55 °C
Permissible ambient temperature range
during storage
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6/EN 60068-2-27, see also
Installation instructions for enhanced mechanical load capacity
[
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
Summary of Contents for KL3444