Mounting and wiring
KL3444, KL3448, KL3454 und KL3458
28
Version: 3.2.0
Terminal housing
High Density Housing
Wire size width (single core wires)
0.08 ... 1.5 mm
2
Wire size width (fine-wire conductors)
0.25 ... 1.5 mm
2
Wire size width (conductors with a wire end sleeve)
0.14 ... 0.75 mm
2
Wire size width (ultrasonically “bonded" conductors)
only 1.5 mm
2
Wire stripping length
8 ... 9 mm
5.4.3
Shielding
Shielding
Encoder, analog sensors and actors should always be connected with shielded, twisted paired
wires.
5.4.4
KL3444 - Connection
Fig. 18: KL3444 - Connection
Terminal point no.
Channel
Name
Connection for
1
1
Input 1
Input 1, signal
2
GND
Input 1, ground
3
3
Input 3
Input 3, signal
4
GND
Input 3, ground
5
2
Input 2
Input 2, signal
6
GND
Input 2, ground
7
4
Input 4
Input 4, signal
8
GND
Input 4, ground
Summary of Contents for KL3444