Configuration Software KS2000
KL31x2
35
Version: 2.4.0
Siemens output format (
You can activate Siemens output format here (default: deactivated).
You can deactivate the calibration here (default: activated).
You can deactivate the differential measurement here (default: activated).
Stabilization of calibration active (
You can deactivate the stabilization of the calibration here (default: activated).
Limitation of the measuring range active (
You can deactivate the limitation of the measuring range here (default: activated).
Limit value 1 active (
)
You can activate the limit value 1 here (default: deactivated).
Limit value 2 active (
You can activate the limit value 2 here (default: deactivated).
Register values
User offset (
)
You can specify the user offset between -32768 and 32767 here (default: 0).
User gain (
)
You can specify the user gain between 0 and 65535 here (default: 256, corresponding to a factor of 1).
You can specify the calibration interval for the reference signal here in steps of 100 ms (default: 300 s).
Forced calibration interval (
)
You can specify the interval for the forced calibration here. This interval is always a multiple (default: 3
dez
) of
the calibration interval. The interval for forced calibration when the terminal leaves the factory is therefore
3 x 180 s = 900 s.
Number of stable measured values (
)
You can specify the number of measured values used for the calibration here (default: 50).
Tolerance for measured value stability (
)
You can specify the stable measured value tolerance for the calibration here (default: 5).
You can specify the limit value 1 here (default: 0).