Access from the user program
KL31x2
49
Version: 2.4.0
Key
Bit
Name
Description
default
R32.15* CallibrationDisplay
0
bin
During the calibration, the terminal sets the overload bit
0
bin
1
bin
Compatibility mode: During calibration, the terminal sets the
error bit
.
R32.14* Display StabilityError 0
bin
Stability error is not displayed.
0
bin
1
bin
of the calibration values is achieved,
the terminal indicates this by setting the error bit
(see note below)
Fluctuating measuring signals
Strongly fluctuating measuring signals can make stabilization of the calibration values impossible. In
this case, skip the stabilization and disable it with bit
Bit
Name
Description
default
R32.13 -
reserved
0
bin
R32.12 -
reserved
0
bin
R32.11 disChannel
0
bin
Channel switched on
0
bin
1
bin
Channel switched off
R32.10 enTh2
0
bin
Limit value 2 is not active
0
bin
1
bin
Limit value 2 is active
R32.9
enTh1
0
bin
Limit value 1 is not active
0
bin
1
bin
Limit value 1 is active
R32.8
enOverProt
0
bin
Measuring range limitation not active
1
bin
1
bin
Measuring range limitation active
R32.7
enStable
0
bin
of the calibration value not active
1
bin
1
bin
of the calibration value active
R32.6
disDiffMeasure
0
bin
Differential measurement active
0
bin
1
bin
Differential measurement not active (only KL3132, KL3162,
KL3172, KL3182)
R32.5
disCali
0
bin
Cyclic calibration of the A/D converter active
0
bin
1
bin
Cyclic calibration of the A/D converter not active
R32.4
enSiemensFormat
0
bin
Siemens output format not active
0
bin
1
bin
Siemens output format active
R32.3
enAverageFormat
0
bin
Signed amount representation not active
0
bin
1
bin
Signed amount representation active
R32.2
disWdTimer
0
bin
Watchdog timer is active (the watchdog is triggered if no
process data are received for 100 ms)
0
bin
1
bin
Watchdog timer is not active
R32.1
enManScal
0
bin
Manufacturer scaling is not active
KL3162, KL3172,
KL3142, KL3152:
0
bin
1
bin
Manufacturer scaling is active
KL3132, KL3182: 1
bin
R32.0
enUsrScal
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
*) Bit R32.14 and bit R32.15 are only available with the following firmware versions:
• KL3132, KL3152, KL3162, KL3172, KL3182: Firmware version 2B or higher
• KL3142: Firmware version 2C or higher