Version: 3.0.0
4-channel, digital output terminal, 24 V
DC
The KL2404 and KL2424 digital output terminals connect the binary 24 V control signals electrically isolated
with the actuators. The Bus Terminals each contain four channels, whose signal states are displayed by
LEDs. The variants KL2404 and KL2424 have different maximum output currents. The 4-channel Bus
Terminals enable the direct connection of four 2-wire sensors. Four ground connection points are provided.
2.4.1
KL2404, KL2424 – Technical data
Technical data
KL2404
KL2424
Connection technology
2-wire
Number of outputs
4
Nominal voltage
24 V
DC
(-15 %/+20 %)
Load type
ohmic, inductive, lamp load
Max. output current
0.5 A (short-circuit proof) per
channel
2.0 A (short-circuit proof)
Short circuit current
< 2 A
< 70 A
Breaking energy (ind.)
< 150 mJ/channel
< 1.7 J/channel
Reverse polarity protection
yes
Electrical isolation
500 V (K-bus / field voltage)
Current consumption power contacts
typ. 30 mA + load
K-Bus current consumption
typ. 9 mA
Bit width in process image
4 outputs
Configuration
no address or configuration settings required
Weight approx.
70 g
Permissible ambient temperature
during operation
-25°C ... +60°C (extended temperature range)
Permissible ambient temperature
during storage
-40°C ... +85°C
Permissible relative humidity
95%, no condensation
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity
[
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Approvals
CE, cULus,
, GL