Product overview
KL2xxx and KS2xxx
10
Version: 3.0.0
Two-channel, digital output terminal, 24 V
DC
The KL2012, KL2022 and KL2032 digital output terminals connect the binary control signals from the
automation unit on to the actuators at the process level with electrical isolation. The KL2012 and KL2022
versions handle different load currents, and their outputs are protected against overload (only KL2012) and
short circuit. The KL2032 Bus Terminal is protected against reverse polarity connection. The Bus Terminals
contain two channels that indicate their signal state by means of light emitting diodes.
2.2.1
KL2012, KL2022, KL2032 - Technical data
Technical data
KL2012, KS2012
KL2022, KS2022
KL2032, KS2032
Connection technology
4 wire
Number of outputs
2
Nominal voltage
24 V
DC
(-15 %/+20 %)
Load type
ohmic, inductive, lamp load
Max. output current (per channel)
0.5 A (short-circuit
proof)
2.0 A (short-circuit
proof)
0.5 A (short-circuit
proof)
Max. short-circuit current
< 2 A
< 70 A
< 2 A
Inductive breaking energy max.
< 150 mJ/channel
< 1.7 J/channel
< 150 mJ/channel
Reverse polarity protection
no
no
yes
Electrical isolation
500 V (K-bus / field voltage)
Current consumption via K-bus
typ. 5 mA
Current consumption power contacts
typ. 15 mA + load
typ. 20 mA + load
typ. 20 mA + load
Bit width in process image
2 outputs
Configuration
no address or configuration settings required
Dimensions (W x H x D)
15 mm x 100 mm x 70 mm (width aligned 12 mm)
Weight
approx. 55 g
Permissible ambient temperature
during operation
0°C ... +55°C
-25°C ... +60°C
(extended
temperature range)
Permissible ambient temperature
during storage
-25°C ... +85°C
-40°C ... +85°C
Permissible relative humidity
95%, no condensation
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity
[
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Pluggable wiring
for all KSxxxx Bus Terminals
Markings / Approvals
CE, cULus,