![Beckhoff EP6224 Documentation Download Page 17](http://html1.mh-extra.com/html/beckhoff/ep6224/ep6224_documentation_2719259017.webp)
Product overview
EP6224 and EP6228
17
Version: 1.5
2.4.2
Technical data
All values are typical values at 25 °C, unless otherwise stated.
Technical data
EP6228-0022
EP6228-3032
EP6228-3132
Fieldbus
Fieldbus
EtherCAT
Connection
2 x M8 socket, green
Electrical isolation
500 V (fieldbus / IO)
Supply voltages
Connection
Power supply:
1 x M8 plug, 4-pin
Downstream connection:
1 x M8 socket, 4-pin
Power supply:
1 x 7/8" plug, 5-pin
Downstream connection:
1 x 7/8" socket, 5-pin
Control voltage U
S
Nominal voltage
24 V
DC
(-15 % / +20 %)
Consumers
• Module electronics: 130 mA
• IO-Link devices: Sensor/logic supply L+
Sum current
max. 4 A
1)
max. 16 A
1)
Peripheral voltage U
P
Nominal voltage
24 V
DC
(-15 % / +20 %)
Consumers
-
IO-Link devices class B:
Actuator supply P24
Sum current
max. 4 A
1)
max. 16 A
1)
IO-Link
Number of ports
8 x Class A
8 x Class B
4 x Class A (ports 1, 2, 5, 6)
4 x Class B (ports 3, 4, 7, 8)
Connection
8 x M12 socket
Cable length
max. 20 m
Specification
IO-Link V1.1
Transmission rate
COM1: 4,8 kbit/s
COM2: 38,4 kbit/s
COM3: 230,4 kbit/s
Sensor/logic supply L+
24 V
DC
from the control
voltage U
S
max. 1.4 A per port
max. 4.0 A in total
24 V
DC
from the control voltage U
S
max. 4.0 A per port
max. 16.0 A in total
Actuator supply P24
(Ports class B)
-
24 V
DC
from peripheral voltage U
P
max. 4.0 A per port pair
2)
max. 16.0 A in total
Environmental conditions
Ambient temperature
during operation
-25 .. +60 °C
0 .. +55 °C according to cURus
Ambient temperature
during storage
-40 .. +85 °C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP65, IP66, IP67 conforms to EN 60529
Mechanics
Weight
approx. 250 g
approx. 450 g
Mounting position
variable
Approvals and conformity
Approvals
CE, cURus
CE, cURus in preparation
1)
Sum current of consumers and power transmission. This value corresponds to the
current carrying capacity of the connections for the supply voltages.
2)
Port pairs with common limitation of the actuator supply:
• EP6228-3032: Port pair 1+5, 2+6, 3+7, 4+8
• EP6228-3132: Port pair 3+7, 4+8
Summary of Contents for EP6224