Product overview
EP4174-0002
11
Version: 1.1.0
2.3
EP4174-0002 - Technical data
Technical data
EP4174-0002
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of outputs
4
M12 sockets
Signal type
Configurable:
0…+10 V
-10…+10 V
0…20 mA
4…20 mA
Load
> 5 kΩ | < 500 Ω
Resolution
16 bit (including sign)
Conversion time
< 4 ms
Measuring error
< 0,1 % (relative to full scale value)
Supply of the module circuitry
From the control voltage Us
Current consumption of the module circuitry
typically 120 mA
Sensor supply
from load supply voltage Up, DC, any value up to 30 V
Power supply connection
Power supply: 1 x M8 plug, 4-pin
Onward connection: 1 x M8 socket, 4-pin
Process image
Outputs: 4 x 16 bit
Electrical isolation
Control voltage / fieldbus: yes
Permissible ambient temperature during
operation
-25°C ... +60°C
0°C ... +55 °C (according to cULus, see
0°C ... +55°C (according to ATEX, see
Permissible ambient temperature during
storage
-25°C ... +85°C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP65, IP66, IP67 (according to EN 60529)
Approvals
Installation position
variable
Summary of Contents for EP4174-0002
Page 2: ......