Commissioning
EL6652-00x0
119
Version: 2.5
Fig. 146:
Selection of the ETHERNET MODULE "Generic Ethernet Module"
Enter the IP address from object 0x8000:21. The input instance is to be entered as 129
dec
, the output
instance as 130
dec
and the config instance as 128
dec
. The data length is dependent on the Comm format. INT
was selected in the illustration
"Transferring the parameters into the "New modules" mask"
, therefore the
number of data items from objects 0x8001:05 and 0x8001:07 must be divided once again by 2, since these
are specified in TwinCAT in bytes and on the RSLogix in Word length (INT). If an odd number of bytes is
created you must round up; this also applies even if the Comm format is set to DINT, in which case you must
round up to the next whole number.