Diagnosis
EL6652-00x0
129
Version: 2.5
Error Codes EL6652
Error
Code
Description
Remedy
CN_ORC_ALREADY_US
ED
0x100 hex / 256 dec
Connection already in use The connection is already
established; use another
connection or close this
one
CN_ORC_BAD_TRANSP
ORT
0x103 hex / 259 dec
Transport type not
supported
CN_ORC_OWNER_CON
FLICT
0x106 hex / 262 dec
More than one guy
configuring
CN_ORC_BAD_CONNEC
TION
0x107 hex / 263 dec
Trying to close inactive
conn
CN_ORC_BAD_CONN_T
YPE
0x108 hex / 264 dec
Unsupported connection
type
The connection type is not
supported, check your
settings
CN_ORC_BAD_CONN_S
IZE
0x109 hex / 265 dec
Connection size mismatch The connection size does
not match, check your
settings
CN_ORC_CONN_UNCO
NFIGURED
0x110 hex / 272 dec
Connection unconfigured
CN_ORC_BAD_RPI
0x111 hex / 273 dec
Unsupportable RPI
The task time usually
doesn't match; make sure
that the EL6652 operates
internally with 1 ms and
that you can adjust this
with the Cycle Time
Multiplier. Otherwise,
adapt the task time to suit.
CN_ORC_NO_CM_RES
OURCES
0x113 hex / 275 dec
Conn Mgr out of
connections
CN_ORC_BAD_VENDOR
_PRODUCT
0x114 hex / 276 dec
Mismatch in electronic key
CN_ORC_BAD_DEVICE_
TYPE
0x115 hex / 277 dec
Mismatch in electronic key
CN_ORC_BAD_REVISIO
N
0x116 hex / 278 dec
Mismatch in electronic key
CN_ORC_BAD_CONN_P
OINT
0x117 hex / 279 dec
Nonexistant instance
number
CN_ORC_BAD_CONFIG
URATION
0x118 hex / 280 dec
Bad config instance
number
CN_ORC_CONN_REQ_F
AILS
0x119 hex / 281 dec
No controlling connection
open
CN_ORC_NO_APP_RES
OURCES
0x11A hex / 282 dec
App out of connections
No further free connection
available
If you cannot fix this error yourself, Support will require the following information:
EDS file of the slave, TwinCAT Build, firmware version of the EL6652 and a Wireshark recording (please
make this using a switch with port mirroring or a hub).