Product overview
EL10xx, EL11xx
30
Version: 4.5
2.5.2
EL1104, EL1114 - Technical data
Technical data
EL1104
EL1114
Number of inputs
4
Number of simultaneously controllable inputs, de-
pending on the ambient temperature
4 (-25°C ... +55°C)
2 (> +55°C )
4 (0°C ... + 55°C)
Nominal voltage of the inputs
24 V
DC
(-15% / +20%)
Signal voltage "0"
-3 V ... 5 V (EN 61131-2, type 1/3)
Signal voltage "1"
11 V ... 30 V (EN 61131-2, type 1/3)
Input filter
3 ms
10 µs typ. (10...50 µs)
Input current
typically 3 mA (EN 61131-2, type 1/3)
Current consumption power contacts
typ. 2 mA + load
Current consumption from the E-bus
typ. 90 mA
Electrical isolation
500 V (E-bus/field voltage)
Bit width in the process image
4 input bits
Configuration
no address setting, configuration via TwinCAT System Manager
Weight
approx. 55 g
Permissible ambient temperature range during op-
eration
-25°C ... +60°C
(extended temperature range)
0°C ... + 55°C
Permissible ambient temperature range during
storage
-40°C ... +85°C
-25°C ... + 85°C
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
according to EN 60068-2-6/EN 60068-2-27,
see also
Installation instructions for terminals with increased mechanical load ca-
EMC resistance burst/ESD
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE,
,