Product overview
EL10xx, EL11xx
18
Version: 4.5
2.1.4
EL1002, EL1004-00x0, EL1008 - Technical data
Technical data
EL1002
EL1004
EL1004-0020
EL1008
Number of inputs
2
4
8
Number of simultaneously controllable in-
puts, depending on the ambient tempera-
ture
2 (> +55°C )
4 (-25°C ... +55°C)
2 (> +55°C )
8 (-25°C ... +55°C)
4 (> +55°C )
(aligned in
Nominal voltage of the inputs
24 V
DC
(-15% / +20%)
Signal voltage "0"
-3 V ... 5 V (EN 61131-2, type 1/3)
Signal voltage "1"
11 V ... 30 V (EN 61131-2, type 1/3)
Input filter
3 ms
Input current
typically 3 mA (EN 61131-2, type 1/3)
Current consumption power contacts
typ. 2 mA + load
Current consumption via E-bus
typ. 90 mA
Electrical isolation
500 V (E-bus/field voltage)
2500 V functional iso-
lation (test voltage E-
bus / field voltage,
production test).
500 V (E-bus/field volt-
age)
Bit width in the process image
2 input bits
4 input bits
8 input bits
Configuration
no address setting, configuration via TwinCAT System Manager
Weight
approx. 55 g
Permissible ambient temperature range
during operation
-25°C ... +60°C
(extended temperature range)
0°C ... +55°C
-25°C ... +60°C
(extended temperature
range,
aligned in
-25°C ... +45°C
(all
)
Permissible ambient temperature range
during storage
-40°C ... +85°C
-25°C ... +85°C
-40°C ... +85°C
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
according to EN 60068-2-6/EN 60068-2-27,
see also
Installation instructions for termi-
nals with increased mechanical load capac-
ity [
according to EN
60068-2-6/EN
60068-2-27
according to EN
60068-2-6/EN
60068-2-27,
see also
structions for terminals
with increased mechani-
cal load capacity [
EMC resistance burst/ESD
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
see
Approval
CE,
,
, IECEx