PROFIBUS DP communication
BK3xx0
57
Version: 4.3.0
PROFIBUS coupler data (Slot_Number = 0)
The data associated with the PROFIBUS coupler is addressed via an index:
Index
Access Description
1-2
R/W
Module assignment in multi-configuration mode [
5
R
9-19
R/W
(Table 9)
90
R
(Table 90)
98
R/W
99
W
starting or stopping the internal cycle time
Function module data (Slot_Number > 0)
Depending on the type of function module, access is made either to the registers (max. 4 channels, each
with 64 registers) or to the parameters (only supported by a few function modules, where the quantity of data
is insufficient for the register model)
Accessing registers
Index
Access Length Description
0-63
R(/W)
2
Registers 0-63 of the channel 1 in the function module
64-127
R(/W)
2
Registers 0-63 of the channel 2 in the function module
128-191 R(/W)
2
Registers 0-63 of the channel 3 in the function module
192-254 R(/W)
2
Registers 0-63 of the channel 4 in the function module
Accessing parameters
Index
Access
Length
Description
0
R(/W)
4-32 (must be divisible by 4)
Parameters 0x0000-0x0007 of the function
module
1
R(/W)
4-32 (must be divisible by 4)
Parameters 0x0008-0x000F of the function
module
...
...
...
127
R(/W)
4-32 (must be divisible by 4)
Parameters 0x03F8-0x03FF of the function
module
5.2.2
Assignment of the DPV1 slot number
The Slot_Number = 0 addresses the data of the Bus Coupler, while Slot_Number > 0 addresses the data
(registers or parameters (KL6201)) of the complex terminals:
Device
Slot number = 0
Slot number > 0
BK3120,
BK3150,
BK3500, BK3520
Data in Bus Coupler
Slot_Number = 1:
first complex terminal plugged into the Bus Coupler
(KL15xx, KL25xx, KL3xxx, KL4xxx, KL5xxx, KL6xxx,
KL8xxx)
Slot_Number = 2:
second complex terminal plugged into the Bus Coupler
(KL15xx, KL25xx, KL3xxx, KL4xxx, KL5xxx, KL6xxx,
KL8xxx)
etc.
BK3x10/LC3100
Data in Bus Coupler
Not present, because neither the BK3x10 nor the LC3100
support complex terminals.