Diagnostics and error handling
BK3xx0
62
Version: 4.3.0
DIA-LED blink codes
If an error occurs in the paramétrisation or configuration during
through the fieldbus LEDs and in the diagnostic data.
Flashing Code
fast blinking
Start of the error code
First slow sequence
Error code
Second slow sequence
Error argument (error location)
Fig. 45: LEDs LC3100
LC3100
I/O RUN
BF
RUN Meaning
Remedy
on
off
on
Operating state: RUN, inputs are read
and outputs are set
Everything is operating correctly
on
on,
blinking
on
1. Bus activity, but slave is already
parameterized
Start master
2. Bus error with reaction to
PROFIBUS error:
a.) K-bus outputs become 0 or b.) K-
bus outputs are retained
Check parameters, configuration
(
possible error in DP start-up [
)
off
off
on
Data exchange with the master is not
started
PLC start
off
on
off
No bus activity
Start the master, check the bus cable
off
on,
blinking
on
Bus error with reaction to PROFIBUS
error: K-bus cycle is stopped
Start master, check parameters,
configuration (
)