Section: GENERAL INFORMATION
4
Professional Installer’s Responsibility:
Specifications
Concealed damage – If you
discover damage to the burner
or controls during unpacking, notify the carrier at
once and file the appropriate claim forms. Do not
install a burner or control that has been damaged.
Special Requirements:
When contacting Beckett for service information —
Please have the burner serial number and contractor
start-up form available when calling or writing. You
will find the serial number on the label located on the
left rear of the burner.
Fire Hazard: Overheating
Should over-heating occur:
•
Shut off the manual gas control to
the appliance.
•
DO NOT shut off power to the
equipment, allow the blower and pumps
to continue running.
If any of these instructions are not clear,
Call Beckett at
1-800-645-2876
for assistance.
Table 1 –
Burner Specifications
Input Firing Rate Available
*
300 - 1200 MBH
Firing Mode
On-Off or On/Off with Low Fire Start
Fuel
Natural gas - 0.64 specific gravity
LP gas - 1.53 specific gravity
Required Gas Supply
Pressure (to gas train)
6” WC minimum (std)
4.5” WC minimum (special)
Input Voltage
**
120 Vac + 10% / -15%; 60 Hz
Input Current
5.3 Amp
Gas Train
24V Valves High/Low gas pressure
switch
Life Cycle
Gas valves are rated for 100-000
cycles (regarding valve seat leakage).
Application Type
Indoor, Stationary. See notice below
for outdoor use.
Burner Control
Programmable Pre-purge
Flame Detection
Flame Rectification
Igniter
Electronic - Direct Spark
Motor
Thermally Protected - Manual Reset
Combustion Air Proving
Differential Pressure Switch
Weight
40 lbs.
Mounting Orientation
Up to 90° from upright with motor
shaft horizontal
Dimensions
11.9” x 16.0” x 20.5”
Acceptable Ambient
Temperature Range
-4°F to +104°F
Acceptable Ambient
Humidity
5% - 95% RH non-condensing
*
For altitudes higher than 2,000 feet, derate the burner capacity 4%
for each 1,000 feet above sea level.
**
This burner is not approved for use in 50 Hz applications.
This burner is UL listed for use
in the US or Canada per ANSI/UL
295 & CSA /CGA 3.4. For use with
natural gas or propane.
Table 2 –
Available Models
Model No.
Input Firing Rate (MBH)
CG10.1
300-378
CG10.2
379-476
CG10.3
477-600
CG10.4
601-756
CG10.5
757-952
CG10.6
953-1,200
CG10.1S
300-378
CG10.2S
379-476
CG10.3S
477-600
CG10.4S
601-756
CG10.5S
757-952
CG10.6S
953-1,200
Explosion, Fire, and
Asphyxiation Hazard
Professional Service Required.
•
Please read all instructions before proceeding.
Follow all instructions completely.
•
This equipment must be installed, adjusted
and started by a qualified service agency that
is licensed and experienced with all applicable
codes and ordinances and responsible for the
installation and commissioning of the equipment.
•
The installation must comply with all local codes
and ordinances having jurisdiction and the latest
edition of the National Fuel Gas Code ANSI
Z223.1 (NFPA 54) and CAN1-B149.1 in Canada.
•
Burner must be used within the limits of
Table 1
.
FOR OUTDOOR USAGE it is the
responsibility of the OEM
equipment manufacturer to protect the burner
system and components from exposure to water in
the end-use application.