Smith Cast Iron Boilers
28
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
28-4
CF1400
BCF205
CF66KE
8.00
5.00x45P
2
40
70
150
300
51629
4.875"
28-5
CF1400
BCF205
CF66KE
10.25
6.00x45P
4
40
90
150
300
51629
4.875"
28-6
CF2300A
BCF304
CF66KG
12.50
7.50x45P 1-1/2
20
40
150
300
51630
4.875"
28-7
CF2300A
BCF304
CF66KG
15.00
9.00x45P 3-1/2
30
55
150
300
51630
4.875"
28-8
CF2300A
BCF304
CF66KG
17.50
10.00x45P
5
30
60
150
300
51630
4.875"
28-9
CF2300A
BCF304
CF66KS
19.60
11.00x45P
3
30
70
150
300
51630
4.875"
28-10
CF2500
BCF1801
CF66KP
22.50
6.50x45P (2)
6
20
40
300
300
51630
4.875"
28-11
CF2500
BCF1801
CF66KP
24.25
7.00x45P (2)
8
27
90
300
300
51630
4.875"
28-12
CF3500A
BCF1301
CF80KM
27.50
8.00x45P (2)
7
30
90
300
300
51630
4.875"
28-13
CF3500A
BCF1301
CF114KR
29.90
9.00x60P (2)
7
50
100
300
300
51631
5.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Smith Cast Iron Boilers
BB-14
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
L-7
CF500
BCF809
CF60KK
3.00
2.50x45PLP
3
3
0
N/A
140
51311
2.25"
H-7
CF500
BCF809
CF60KK
3.40
3.00x45PLP
3
4
0
N/A
140
51311
2.25"
L-8
CF500
BCF809
CF60KK
3.50
3.00x45PLP
3
5
0
N/A
140
51311
2.25"
H-8
CF500
BCF809
CF60KK
4.00
3.25x45PLP
5
8
0
N/A
140
51311
2.25"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 27
Summary of Contents for BRYAN STEAM CF2300A
Page 35: ......