Weil McLain
88
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
488R
CF1400
BCF205
CF66KD
6.90
4.00x70B
1
30
120
125
300
51629
4.00"
488
CF1400
BCF205
CF66KD
7.00
4.00x70B
1
30
120
125
300
51629
4.00"
588
CF1400
BCF205
CF66KD
9.40
5.50x70B
3
40
120
125
300
51629
4.00"
688
CF2300
BCF304
CF66KG
11.80
6.50x60B
2
20
30
125
300
51630
4.00"
788
CF2300A
BCF304
CF66KG
14.20
8.00x60B
3
20
30
125
300
51630
4.00"
888
CF2300A
BCF304
CF66KG
16.60
9.50x60B
5
30
60
125
300
51630
4.00"
988R
CF2300A
BCF304
CF66KG
17.20
10.00x60B 8-1/2
38
95
125
300
51630
4.00"
988
CF2300A
BCF304
CF66KS
18.20
11.00x45P 1-1/2
38
63
150
275
51630
4.00"
1088R
CF2300A
BCF304
CF66KS
19.90
12.00x45P
2
40
65
150
275
51630
4.00"
1088
CF2500
BCF1801
CF66KP
21.50
6.00x60B (2)
2
18
40
300
300
51630
4.00"
1188
CF2500
BCF1801
CF66KP
23.50
6.50x60B (2)
4
20
40
300
300
51630
4.00"
1288
CF3500
BCF1301
CF80KM
26.00
7.50x60B (2)
7
24
60
300
300
51630
4.50"
1388
CF3500
BCF1301
CF80KM
28.50
8.50x60B (2)
7
26
70
300
300
51630
4.50"
1488
CF3500
BCF1301
CF114KR
29.90
9.00x60B (2)
7
50
100
300
300
51631
5.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 32
Summary of Contents for BRYAN STEAM CF2300A
Page 35: ......