Easco Boiler
ESP
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
70
CF2500
BCF1801
CF102KP
21.00
6.00x45P (2)
5
10
50
300
300
51630
5.00"
80
CF3500
BCF1301
CF80KM
24.00
6.50x45P (2)
2
20
80
300
300
51630
5.00"
90
CF3500
BCF1301
CF114KR
27.00
7.50x45P (2)
6
25
85
300
300
51631
5.00"
100
CF3500
BCF1301
CF114KR
30.00
8.50x45P (2)
7
35
95
300
300
51631
5.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Flange requires an additional adapter plate.
Easco Boiler
FST
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
20
CF800
BCF403
CF100KH
6.00
4.50x45P
3
10
3
N/A
150
51628
5.00"
20
CF1400
BCF205
CF102KE
6.10
3.50x45P
1/2
20
40
150
300
51629
5.00"
32
CF1400
BCF205
CF102KE
9.60
5.50x45P
4
35
70
150
300
51629
5.00"
40
CF2300A
BCF304
CF102KG
12.00
6.50x45P
1
17
30
150
300
51630
5.00"
50
CF2300A
BCF304
CF102KG
15.60
8.50x45P
4
35
75
150
300
51630
5.00"
60
CF2300A
BCF304
CF102KG
18.00
10.00x45P
5
30
60
150
300
51630
5.00"
70
CF2500
BCF1801
CF102KP
21.00
6.00x45P (2)
5
20
50
300
300
51630
5.00"
80
CF3500
BCF1301
CF80KM
24.00
6.50x45P (2)
2
20
80
300
300
51630
5.00"
90
CF3500
BCF1301
CF114KR
27.00
7.50x45P (2)
6
25
85
300
300
51631
5.00"
100
CF3500
BCF1301
CF114KR
30.00
8.50x45P (2)
7
35
95
300
300
51631
5.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Flange requires an additional adapter plate.
Page 15
Summary of Contents for BRYAN STEAM CF2300A
Page 35: ......