75.5351.02  EN   20080317   (75.5350) 

Page 7 of 7 

 

 
 
During the manual adjustment session: 

 Each press on the 

right button

 

increases the number of the displayed parameter

 by one unit; 

 Each press on the 

left button increases the value of the displayed parameter

 by one unit.  

NOTE:  When the maximum value or the highest number of the parameter is reached, this will return 

to their minimum values.  

 

Parameter 

Number 

Parameter Values Factory 

setting 

Sensitivity 

0 - 9 

Hold time 

0 - 9 

Relay configuration 

1 - 4 

Detection mode 

1 - 3 

5 Pedestrian 

rejection mode 

1 - 5 

  For example, to change the sensitivity from 7 to 9 and the rejection mode from ‘detection of all kind of 

targets in motion’ to High ‘Pedestrian/parallel traffic’ rejection.  

 Press any button for 2 seconds to enter the adjustment session and then release it. 

 The red LED flashes once (parameter 1 = sensitivity) and the green LED flashes 7 times (sensitivity=7). 

 Press the left button twice to increase the sensitivity from 7 to 9. 

• 

The red LED still flashes once (parameter 1 = sensitivity) but the green LED flashes 9 times now 

(sensitivity=9). 

 Now press the right button 4 times to move to function 5 (rejection mode) ; 

 The red LED flashes 5 times (parameter 5 = rejection mode) and the green LED flashes once 

(‘detection of all kind of targets in motion’

) ; 

 Press the left button 4 times to set the parameter to High ‘Pedestrian/parallel traffic’ rejection.  

 The red LED still flashes 5 times (parameter 5 = rejection mode) but the green LED flashes 5 times now 

(High ’Pedestrian/parallel traffic’ rejection). 

 Press any button during 2 seconds to end the adjustment session and then release it. 

 

 
 

SYMPTOM 

PROBABLE CAUSE 

CORRECTIVE ACTION 

The door will not open and the red 
LED does not light up. 

The sensor power is off. 

Check power supply. 
Check the supply voltage. 

The sensor ‘sees’ the door 
moving. 

Increase the tilt angle and/or reduce 
the sensitivity. 

The door opens and closes 
constantly. 

When closing the door creates 
vibrations picked up by the 
sensor. 

Ensure that the sensor is correctly 
fixed. 
If the rejection mode is set at level 1, 
set this parameter to level 2. 
Reduce the sensitivity. 
Switch to unidirectional mode. 

The door opens and closes after a 
given time for no apparent reason. 

The sensor is picking up 
unintended traffic motion. 

Reduce the sensitivity. 
Reduce the tilt angle. 

The sensor is not capable of 
activation near the door. 

The tilt angle is too large. 

Reduce the tilt angle. 

The batteries are weak. 
 

Check the batteries insertion. 
Change the batteries. 

The sensor does not respond to the 
remote control. 

The access code has been 
changed. 

 Press both push buttons 

simultaneously to reset all the 
parameters to the factory values. 

 Or switch off the power supply. 

Within the first minute after the 
power on, change the access code.

 

 
 

 

 

 

TROUBLE-

SHOOTING

 

 

TROUBLE-

SHOOTING

 

 

Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, 
please call BEA, Inc.  If you must wait for the following workday to call BEA, leave the door inoperable until 
satisfactory repairs can be made.   Never sacrifice the safe operation of the automatic door or gate for an 
incomplete solution. 

 
 

 

The following numbers can be called 24 hours a day, 7 days a week.  For more information, visit www.beasensors.com. 

 

 
 
 

US & Canada: 1-866-249-7937 

Midwest: 1-888-308-8843 

Northeast: 1-866-836-1863

 

West: 1-888-419-2564 

Southeast: 1-800-407-4545 

Canada: 1-866-836-1863 

 
 

 

Summary of Contents for Falcon

Page 1: ... current 1A resistive Max switching power 30W DC 60 VA AC Hold time 0 5s to 9s adjustable Manual adjustment orientation of sensing field mechanically multiple functions by push buttons Remote control adjustments Sensitivity Hold time Detection mode Pedestrian and parallel traffic rejection mode Relay configuration Temperature range 22 F to 122 F 30 C to 60 C Degree of protection IP65 Product confo...

Page 2: ...housing slot guides Gently push the front cover and make sure that the external housing is properly seated front cover must be flush with housing Screw the 2 front cover screws and tighten the retaining nut Ceiling Mounting Wall Mounting Remark The bold type values give the minimum distance required to be able to fully adjust the sensor Check that both locking collar are at the same angle Align th...

Page 3: ...following adjustments tilt angle 15 30 45 sensitivity 9 The sensing fields here on the right correspond to the following adjustments tilt angle 30 sensitivity 9 6 3 When the power is turned ON the red and green LEDs flash for few seconds During a detection the red LED lights on During configuration the red LED flashes a number of times corresponding to the parameter being changed see next table Th...

Page 4: ...to the 0000 value factory setting or during the first minute after the power on press only the UNLOCK Key 3 no code required UNLOCK with code UNLOCK without code 0000 The red LED flashes quickly waiting for the access code After entering the correct code or if no code is required the red LED flashes slowly to indicate that the unlock is successful and the adjustment session has begun NOTE Adjustme...

Page 5: ...ent session all the parameters may be reset to their factory values in the following way PARAMETER KEY USER S ACTIONS DEFAULT VALUES Press the DEFAULT VALUES Key 12 then press the NUMBER Key 1 All the parameters are reset to the factory values see below DEFAULTS VALUES PARAMETER KEY USER S ACTIONS FACTORY SETTING LED SIGNAL SENSITIVITY Press the SENSITIVITY Key 6 Use the NUMBER Keys 0 9 1 to enter...

Page 6: ...level to obtain the required rejection 2 Unidirectional Approach 1 No rejection The red LED flashes quickly waiting for the value Once this has been entered it flashes slowly again The red LED flashes quickly waiting for the value Once this has been entered it flashes slowly again Without remote control all of the parameters can be set using the 2 push buttons NOTE These two buttons are accessible...

Page 7: ... and then release it SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION The door will not open and the red LED does not light up The sensor power is off Check power supply Check the supply voltage The sensor sees the door moving Increase the tilt angle and or reduce the sensitivity The door opens and closes constantly When closing the door creates vibrations picked up by the sensor Ensure that the sensor is...