background image

 

75.5351.02  EN   20080317   (75.5350) 

Page 3 of 7 

 

 

FALCON (Mounting height: 16.5 feet) 

 
 

 
 
 
 

 
 
 
 
 
 

The sensing fields here on the 
right correspond to the 
following adjustments:     

 tilt angle: 15°, 30°, 45°  

 sensitivity: 9. 

The sensing fields here on the 
right correspond to the following 
adjustments:       

 tilt angle: 30° 

 sensitivity: 9, 6, 3 

 

FALCON (Mounting height: 11.5 feet)

 

 

 
 
 
 
 
 
 
 
 
 
 

The sensing fields here on the 
right correspond to the 
following adjustments:     

 tilt angle: 15°, 30°, 45° ; 

 sensitivity: 9. 

The sensing fields here on the 
right correspond to the 
following adjustments:      

 tilt angle: 30° 

 sensitivity: 9, 6, 3 

 

FALCON XL (Mounting height: 8 feet)

 

 

 
 
 
 
 
 

The sensing fields here on the 
right correspond to the 
following adjustments:     

 tilt angle: 15°, 30°, 45° ; 

 sensitivity: 9. 

The sensing fields here on the 
right correspond to the 
following adjustments:      

 tilt angle: 30° 

 sensitivity: 9, 6, 3 

 

 
 

 

 When the power is turned ON, the red and green LEDs flash for few seconds. 

 

 During a detection the red LED lights on. 

 

 During configuration, the red LED flashes a number of times corresponding to the parameter being 

changed (see next table). The green LED flashes a number corresponding to its setting. 

 
 
 
 

 

SETTING  

THE SENSING 

FIELD 

DIMENSIONS

 

 

 

LED SIGNAL 

6          3           0          3          6

3   

    

12 

15 

18 

21 

3    
 
 

 

    


 
 
12
 
 
15
 
 
18

 

 
21

H = 16.5 ft. 
S = 9

 

 

6          3           0          3          6

3   

    

12 

15 

18 

21 

3    
 
 

 

    


 
 
12
 
 
15
 
 
18

 

 
21

H = 16.5 ft. 
Angle = 30

°

 

 

6          3           0          3          6

3   
 
 

 
     

 
 
12 
 
 
15 
 
 
18 

 

 
21 

3    
 
 

 

    


 
 
12
 
 
15
 
 
18

 

 
21

H = 11.5 ft. 
S = 9

 

 

6          3           0          3          6

H = 11.5 ft. 
Angle = 30

°

 


 
     

 
 

 
 
12 
 
 
15 


 

    


 
 

 
 
12
 
 
15

 

6          3           0          3          6

H = 8 ft. 
S = 9 

 


 
     

 
 

 
 
12 
 
 
15 


 

    


 
 

 
 
12
 
 
15

 

6          3           0          3          6

H = 8 ft. 
Angle = 30

°

 


 
     

 
 

 
 
12 
 
 
15 


 

    


 
 

 
 
12
 
 
15

Summary of Contents for Falcon

Page 1: ... current 1A resistive Max switching power 30W DC 60 VA AC Hold time 0 5s to 9s adjustable Manual adjustment orientation of sensing field mechanically multiple functions by push buttons Remote control adjustments Sensitivity Hold time Detection mode Pedestrian and parallel traffic rejection mode Relay configuration Temperature range 22 F to 122 F 30 C to 60 C Degree of protection IP65 Product confo...

Page 2: ...housing slot guides Gently push the front cover and make sure that the external housing is properly seated front cover must be flush with housing Screw the 2 front cover screws and tighten the retaining nut Ceiling Mounting Wall Mounting Remark The bold type values give the minimum distance required to be able to fully adjust the sensor Check that both locking collar are at the same angle Align th...

Page 3: ...following adjustments tilt angle 15 30 45 sensitivity 9 The sensing fields here on the right correspond to the following adjustments tilt angle 30 sensitivity 9 6 3 When the power is turned ON the red and green LEDs flash for few seconds During a detection the red LED lights on During configuration the red LED flashes a number of times corresponding to the parameter being changed see next table Th...

Page 4: ...to the 0000 value factory setting or during the first minute after the power on press only the UNLOCK Key 3 no code required UNLOCK with code UNLOCK without code 0000 The red LED flashes quickly waiting for the access code After entering the correct code or if no code is required the red LED flashes slowly to indicate that the unlock is successful and the adjustment session has begun NOTE Adjustme...

Page 5: ...ent session all the parameters may be reset to their factory values in the following way PARAMETER KEY USER S ACTIONS DEFAULT VALUES Press the DEFAULT VALUES Key 12 then press the NUMBER Key 1 All the parameters are reset to the factory values see below DEFAULTS VALUES PARAMETER KEY USER S ACTIONS FACTORY SETTING LED SIGNAL SENSITIVITY Press the SENSITIVITY Key 6 Use the NUMBER Keys 0 9 1 to enter...

Page 6: ...level to obtain the required rejection 2 Unidirectional Approach 1 No rejection The red LED flashes quickly waiting for the value Once this has been entered it flashes slowly again The red LED flashes quickly waiting for the value Once this has been entered it flashes slowly again Without remote control all of the parameters can be set using the 2 push buttons NOTE These two buttons are accessible...

Page 7: ... and then release it SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION The door will not open and the red LED does not light up The sensor power is off Check power supply Check the supply voltage The sensor sees the door moving Increase the tilt angle and or reduce the sensitivity The door opens and closes constantly When closing the door creates vibrations picked up by the sensor Ensure that the sensor is...

Reviews: