20. TECHNICAL SPECIFICATIONS
Model: LUNA DUO-TEC MP+
1.35
1.50
1.60
1.70
Cat.
II
2H3P
Gas used
-
G20 - G31
Rated heat input
kW
34,8
46,3
56,6
66,9
Reduced heat input
kW
5,1
5,1
6,3
7,4
Rated heat power 80/60°C
kW
33,8
45
55
65
Rated heat power 50/30 °C
kW
36,6
48,6
59,4
70,2
Reduced heat output 80/60 °C
kW
5,0
5,0
6,1
7,2
Reduced heat output 50/30 °C
kW
5,4
5,4
6,6
7,8
Rated efficiency 50/30 °C
%
105,0
105,0
105,0
105,0
Max. water pressure in heating circuit
bar
4
Min. water pressure in heating circuit
bar
0,5
Temperature range in heating circuit
°C
25÷80
Fumes typology
-
C13 - C33 - C43 - C53 - C63 - C83 - C93 - B23
Coaxial flue duct diameter
mm
80/125
Diameter of separate outlets
mm
80/80
Max. mass flow rate of flue
kg/s
0,016
0,021
0,026
0,031
Min. mass flow rate of flue
kg/s
0,002
0,002
0,003
0,004
Max. temperature of flue
°C
90
92
96
76
Natural gas supply pressure 2H
mbar
20
Propane gas supply pressure 3P
mbar
37
Power supply voltage
V
230
Power supply frequency
Hz
50
Rated power supply
W
180
230
230
230
Net weight
kg
40
40
40
50
Dimensions - height
mm
766
- width
mm
450
- depth
mm
377
377
377
505
Protection-limit against humidity (EN 60529)
-
IPX5D
Capacity of boiler circuit (volume of water)
l
4
4
5
6
EC certificate
Nr.
0085CM0128
CONSUMPTION AT HEAT INPUT Qmax and Qmin
Qmax (G20) - 2H
m
3
/h
3,68
4,90
5,98
7,07
Qmin (G20) - 2H
m
3
/h
0,54
0,54
0,67
0,78
Qmax (G31) - 3P
kg/h
2,70
3,60
4,40
5,20
Qmin (G31) - 3P
kg/h
0,40
0,40
0,49
0,57
Summary of Contents for Luna Duo-Tec MP Plus 1.35
Page 24: ...7221369 01 1 03 15 90 S E C T I O N A 20...
Page 29: ...95 S E C T I O N C 7221369 01 1 03 15 G 3 4 G 1 G 1 95 123 100 100 CR_0774 75 5 51 5 43 22 O...
Page 32: ...7221369 01 1 03 15 98 S E C T I O N F AGU 2 550 CR_0349 CR_0349 AVS 75...
Page 33: ...99 S E C T I O N F 7221369 01 1 03 15 CG_2482 Tmax 50 C...