Use the Remote Control to set the programmable timer for heating and DHW. See the instructions supplied with the accessory.
SETTING PARAMETERS USING THE REMOTE CONTROL
SYMBOLS FOR REMOTE CONTROL
Turn knob
B
Display shows
Press knob
B
Press button
A
and knob
B
together
Press button
A
or
C
Press buttons
A
and
C
together
KEY TO FIGURE MENU
1
Enduser
3
Engineer
2
Commissioning
4
OEM
ALL MODIFIED PARAMETERS SHOULD BE NOTED
DOWN IN THE TABLE AT THE END OF THIS MANUAL.
The following procedure is used to access the four boiler
programming menus:
•
from the main menu
C
.
•
A
and
C
(hold down for approx. 6 seconds)
B
menu
1
-
2
-
3
-
4
(see figure to side and key).
•
C
to go back one menu at a time to the main menu.
When the Control Panel is wall-mounted enable the
room sensor
and
flow temperature modulation
as follows:
A) ROOM SENSOR
•
Access menu
2
.
•
B
Operator unit
B
to confirm.
•
B
programme row
40
(Used as)
B
.
•
B
(anti-clockwise)
Room unit 1
B
to confirm (the room sensor is now active).
•
C
to return to the previous menu then
B
Configuration
B
.
•
B
programme row
5977
(Function input H5) then
B
to confirm.
•
B
None
B
to confirm.
For correct operation of the environment unit during the reduced time band it is necessary to set the parameter 5977 = "none".
B) FLOW TEMPERATURE MODULATION
To set flow temperature modulation, disable parameter
742
(HC1). Proceed as follows:
•
Access menu
2
.
•
B
Temps / mode CH1
B
to confirm
B
742
(Flow temp setpoint room stat)
B
to confirm.
•
B
(anti-clockwise)
"
---
" then
B
to confirm.
If, when turning the knob
B
on the main menu, the display visualises the boiler flow temperature instead of the ambient
temperature, parameter
742
has not been set correctly.
After every system configuration (e.g.: solar combination, connection an external storage boiler, etc.) perform the following
procedure to update the boiler board to the new configuration:
•
Access menu 2 as indicated at the beginning of this section.
•
B
Configuration
B
B
programme row
6200
then
B.
•
B
Yes
then
B
to confirm.
ZONE SYSTEM WITH INSTALLATION OF THE REMOTE CONTROL
The electrical connection and the adjustments required to manage a system divided into zones with use of the Remote Control
differs according on the accessories connected to the boiler. To install and configure, see the instructions of the
Expansion
Module
supplied as an accessory.
ADJUSTING THE TEMPERATURE OF THE HIGH TEMPERATURE HEATING SYSTEM
To avoid frequent starting and stopping, raise the minimum temperature setpoint of the boiler in the heating mode by setting
parameters
740
, to not less than 45°C, using the procedure described in point
B
.
Summary of Contents for luna duo-tec MP+ 1.35
Page 90: ...7221369 01 1 03 15 90 S E C T I O N A 20...
Page 95: ...95 S E C T I O N C 7221369 01 1 03 15 G 3 4 G 1 G 1 95 123 100 100 CR_0774 75 5 51 5 43 22 O...
Page 98: ...7221369 01 1 03 15 98 S E C T I O N F AGU 2 550 CR_0349 CR_0349 AVS 75...
Page 99: ...99 S E C T I O N F 7221369 01 1 03 15 CG_2482 Tmax 50 C...