Check the setting pressure at position 4. No
adjustment to the setting pressure is possible.
Turn the control knob to the
‘
OFF
’
( ) position.
Disconnect the pressure gauge and
replace the pressure test point
sealing screw, ensuring a gas-
tight seal.
Refit the electrical cover.
SPILLAGE DETECTION
A test for clearance of flue products is only
possible from the left hand side and must be made
as follows: Ensure that all doors and windows in the
room are closed.
(If there is an extractor fan or
ceiling fan in the room or any adjoining room, the
check for spillage must be performed with the
fan turned on and any interconnecting doors
open.)
Ignite the fire and turn to setting 4.
After running for 5 minutes take a lighted
smoke match and insert it into the boiler
down-draught diverter as shown.
WARNING
CARE MUST BE TAKEN TO AVOID
TOUCHING HOT PANELS AT THIS POINT.
If the majority of the smoke is not drawn into the
chimney, then spillage of combustion products is
indicated and further investigations must be carried
out.
Repeat the procedure with both the boiler and the fire
alight (the boiler having been alight for 5 minutes).
Smoke
Match
Smoke
Match
18