3 Technical specifications
3.1
Homologations
3.1.1
Directives
This product complies with the requirements of the following European
Directives and Standards:
Pressure Equipment Directive 2014/68/EU
Low Voltage Directive 2014/35/EU
Generic standard: EN 60335-1
Relevant standard: EN 60335-2-40
Electromagnetic Compatibility Directive 2014/30/EU
Generic standards: EN 61000-6-3, EN 61000-6-1
Relevant Standard: EN 55014
This product conforms to the requirements of European Directive
2009/125/EC on the ecodesign of energy-related products.
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines
specified in this manual.
3.1.2
Factory test
Before leaving the factory, each indoor module is tested on the following
items:
Tightness of the heating circuit
Electrical safety
Tightness of the refrigerant circuit
Tightness of the domestic hot water circuit
3.2
Technical data
3.2.1
Heat pump
The specifications are valid for a new appliance with clean heat
exchangers.
Maximum operating pressure: 0.3 MPa (3 bar)
Tab.1
Conditions of use
AWHP 22 TR–2
AWHP 27 TR-2
Limit water operating temperatures in heating mode
+18 °C/+60 °C
+18 °C/+60 °C
Limit outdoor air operating temperatures in heating mode
-20 °C/+35 °C
-20 °C/+35 °C
Limit water operating temperatures in cooling mode
+7 °C / +25 °C
+7 °C / +25 °C
Limit outdoor air operating temperatures in cooling mode
+7 °C/+46 °C
+7 °C/+46 °C
Tab.2
Heating mode: outside air tempe7 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 22 TR–2
AWHP 27 TR-2
Heat output
kW
21.70
24.40
Coefficient of Performance (COP)
3.96
3.80
Absorbed electrical power
kWe
5.48
6.25
Nominal water flow rate (ΔT = 5 K)
m
3
/hour
3.8
4.2